ATH-000029Rawabi · CMR
Generator 1
Location
Basement Gen Room
Status
Operational
Priority
P3 - Routine
Condition grade 2
Good
1
2
3
4
5
FINDINGS & RECOMMENDED ACTION
Generator underwent preventive maintenance and was tested for 10 minutes without load. Oil pressure recorded at 574 kPa, coolant temperature 58°C, frequency 59.9 Hz and voltage 379 V. General inspection and cleaning completed, with accumulated dust removed from the unit. All checked parameters reported within operational limits.
Technical Details
- System
- Electrical
- Category
- Emergency Power
- Manufacturer
- CATERPILLAR
- Model
- SR-4
- Serial Number
- 6NA01426
- Location
- Basement Gen Room