FINDINGS & RECOMMENDED ACTION
Generator underwent preventive maintenance and completed a 10-minute test run without load. Oil pressure recorded at 598 kPa, coolant temperature 61°C, frequency 60.4 Hz and voltage 381 V. General inspection and cleaning completed, with accumulated dust removed. All checked parameters reported within operational limits.
Technical Details
- System
- Electrical
- Category
- Standby Generator
- Manufacturer
- CATERPILLER
- Model
- SR-4
- Serial Number
- 6NA01427
- Location
- Basement
Documents