FINDINGS & RECOMMENDED ACTION

Generator underwent preventive maintenance and completed a 10-minute test run without load. Oil pressure recorded at 598 kPa, coolant temperature 61°C, frequency 60.4 Hz and voltage 381 V. General inspection and cleaning completed, with accumulated dust removed. All checked parameters reported within operational limits.

Technical Details

System
Electrical
Category
Standby Generator
Manufacturer
CATERPILLER
Model
SR-4
Serial Number
6NA01427
Location
Basement

Documents

0

No documents attached.