Air Handling Unit 1
Location
1st Floor ME Room (ER & Pharmacy)
Status
Operational
Priority
P4 - Monitor
Condition grade 3
Fair
1
2
3
4
5
FINDINGS & RECOMMENDED ACTION
{REFER TO ATTACHMENTS FOR EVIDENCE OF FINDINGS AND MEASUREMENTS BELOW) - Rated airflow: 30600 m^3/h > 18,000 CFM. - Unit operating at 25 Hz out of 60 Hz (41% of its maximum operation). - 7,380 CFM (3.5 m^3/s) - PSYCHOMETRIC CALCULATIONS: READINGS AT Pre-coil Temp % RH: 22.2 Celsius @ 34.1% RH: Dry-bulb(Input) 22.2°C RH(Input) 34.1% Humidity ratio 5.65g/kg Enthalpy 36.7kJ/kg Wet-bulb13.1°C Dew point 5.7 °C Specific volume 0.844 m³/kg Density 1.191 kg/m³ Vapor pressure 913Pa READINGS AT Post-coil temp %RH: 17.6 Celsius @ 43% RH: Humidity ratio 5.36g/kg Enthalpy 31.3kJ/kg Wet-bulb10.9°C Dew point 4.9 °C Specific volume 0.831 m³/kg Density 1.210 kg/m³ Vapor pressure 866Pa Calculations: Total cooling = (3.5 m^3/s) * 1.2 kg/m^3 * (36.7 kj/kg - 31.3 kj/kg ) = 22.68 kW / 3.517 = 6.4 TR Sensible cooling = 3.5 m^3/s) * 1.2 kg/m^3 *1.02 kj/kg K * (22.2 CELSIUS - 17.6 CELSIUS) = 19.7 kW / 3.517 = 5.6 TR Latent cooling = Total cooling - Sensible Cooling = 0.80 TR Summary: Total cooling load @ 25 Hz > 6.4 TR Sensible cooling load @ 25 Hz > 5.6 TR Latent cooling load @ 25 Hz > 0.8 TR FINDINGS: -Expected drainage condensate > No condensate at 16.7 Celsius coil surface temp. (shown in psychometric image). -Chilled water temp supply and return is not present on site and on BMS. (No test points). - Give there is no datasheet, Suspected underperformance at supposedly (40 TR rated as per the operator and ASHRAE STANDARDS OF 350-400 CFM/TR), unit is performing about 6.4 TR at 41% of 40 TR rated whereas it is supposed to achieve 16 TR. - Loose connection as shown in images (below) -One belt missing in pulley blower motor system
Technical Details
- System
- Mechanical
- Category
- Air Handling Unit
- Manufacturer
- Carrier
- Model
- 39FD670
- Serial Number
- 881976
- Location
- 1st Floor ME Room (ER & Pharmacy)
Documents
0No documents attached.
Need to update this asset?
Sign in with your technician or administrator account. Your name and every changed field are added to the asset history.
Sign in to update