Air Handling Unit 2
Location
1st floor- ME ROOM
Status
Operational
Priority
P4 - Monitor
Condition grade 2
Good
1
2
3
4
5
FINDINGS & RECOMMENDED ACTION
{REFER TO ATTACHMENTS FOR EVIDENCE OF FINDINGS AND MEASUREMENTS BELOW) - Rated airflow: 30600 m3/h > 18,085 CFM. - Unit operating at 50 Hz out of 60 Hz (83.3% of its maximum operation). - 83% * 18,000 CFM = 14,940 CFM (7.0 m^3/s) - PSYCHOMETRIC CALCULATIONS: READINGS AT Pre-coil Temp & % RH: 32.2 Celsius @ 20.5% RH: Dry-bulb(Input) 32.2 °C RH(Input) 20.5 % Humidity ratio 6.12 g/kg Enthalpy 48.1 kJ/kg Wet-bulb 17.2 °C Dew point 6.8 °C Specific volume 0.874 m³/kg Density 1.152 kg/m³ Vapor pressure 987 Pa READINGS AT Post-coil temp & %RH: 14.1 Celsius @ 54.5% RH: Dry-bulb(Input) 14.1 °C RH(Input) 54.5 % Humidity ratio 5.43 g/kg Enthalpy 27.9 kJ/kg Wet-bulb 9.4 °C Dew point 5.1 °C Specific volume 0.821 m³/kg Density 1.225 kg/m³ Vapor pressure 877 Pa Calculations: Total cooling = (7.0 m^3/s) * 1.2 kg/m^3 * (48.1 kj/kg - 27.9 kj/kg ) = 169.7 kW / 3.517 = 48.2 TR Sensible cooling = (7.0 m^3/s) * 1.2 kg/m^3 * (32.2 CELSIUS - 14.1 CELSIUS) = 152.04 kW / 3.517 = 43.2 TR Latent cooling = Total cooling - Sensible Cooling = 5 TR - Surface coil temp > 3.2 Celsius...Dew point> 6.8 Celsius> Condensate forms (Confirmed). Summary of calculations: Knowing that the unit has a nominal capacity of 60 TR and 50/60 Hz is 83% of 60 TR is 49.8 TR: Total cooling load @ 50 Hz > 48.2 TR Sensible cooling load @ 50 Hz > 43.2 TR Latent cooling load @ 50 Hz > 5 TR Unit is in excellent performance condition. -Chilled water temp supply and return is not present on site and on BMS. (No test points). - Given there is no technical datasheet, the unit is performing perfectly @52 Hz achieving 35.9 TR based on 45 TR (as per operator and ASHRAE 350-400 CFM/TR standards). - Retain unit
Technical Details
- System
- Mechanical
- Category
- Air Handling Unit
- Manufacturer
- Carrier
- Model
- 39FD670
- Serial Number
- 881977
- Location
- 1st floor- ME ROOM
Documents
0No documents attached.
Need to update this asset?
Sign in with your technician or administrator account. Your name and every changed field are added to the asset history.
Sign in to update