Air Handling Unit 3
Location
1st floor- ME ROOM
Status
Operational
Priority
P4 - Monitor
Condition grade 2
Good
1
2
3
4
5
FINDINGS & RECOMMENDED ACTION
{REFER TO ATTACHMENTS FOR EVIDENCE OF FINDINGS AND MEASUREMENTS BELOW) - Capacity: 29614 m3/h > 17,502 CFM > 8.2 m3/s - Airflow at 55 Hertz out of 60 (91.6%) > 16,031 CFM > 7.5 m3/s - PSYCHOMETRIC CALCULATIONS: READINGS AT Pre-coil Temp & % RH: 33.7 Celsius @ 18% RH: Dry-bulb(Input) 33.7 °C RH(Input) 18.0 % Humidity ratio 5.84 g/kg Enthalpy 48.9 kJ/kg Wet-bulb 17.5 °C Dew point 6.1 °C Specific volume 0.877 m³/kg Density 1.146 kg/m³ Vapor pressure 942 Pa READINGS AT Post-coil temp & %RH: 13.9 Celsius @ 50% RH: Dry-bulb(Input) 13.9 °C RH(Input) 50.0 % Humidity ratio 4.91 g/kg Enthalpy 26.4 kJ/kg Wet-bulb 8.8 °C Dew point 3.7 °C Specific volume 0.820 m³/kg Density 1.226 kg/m³ Vapor pressure 794 Pa Calculations: Total cooling = (7.5 m^3/s) * 1.2 kg/m^3 * (48.9 kj/kg - 26.4 kj/kg ) = 202.5 kW / 3.517 = 57.6 TR Sensible cooling = (7.5 m^3/s) * 1.2 kg/m^3 * (33.7 CELSIUS - 13.9 CELSIUS) = 178.2 kW / 3.517 = 50.7 TR Latent cooling = Total cooling - Sensible Cooling = 6.9 TR Surface coil temp > 3.4 Celsius. Dew point>6.1 Celsius...Condensate FORMS. Summary of calculations: Total cooling load @ 55 Hz > 57.6 TR Sensible cooling load @ 55 Hz > 50.7 TR Latent cooling load @ 55 Hz > 6.9 TR Motor amperage > 13.6 Amps @ 55 Hz Findings: Unit is performing 57.6 TR out of expected 55 TR (55/60 Hz of 60 TR nominal estimated Capacity). - Retain Unit
Technical Details
- System
- Mechanical
- Category
- Air Handling Unit
- Manufacturer
- Carrier
- Model
- 39FD670
- Serial Number
- 881978
- Location
- 1st floor- ME ROOM
Documents
0No documents attached.
Need to update this asset?
Sign in with your technician or administrator account. Your name and every changed field are added to the asset history.
Sign in to update