AtharAssetAsset Record
ATH-000076Rawabi · CMR

Air Handling Unit 4

Location

1st floor- ME ROOM

Status

Operational

Priority

P4 - Monitor

Condition grade 2

Good

1

2

3

4

5

FINDINGS & RECOMMENDED ACTION

- Given there is no technical datasheet and only airflow rating, the unit's nominal cooling capacity is 10 TR ( TR = 3,389 CFM / 350 TR) Based on ASHRAE's rule of thumb of 350-400 CFM/TR comfort cooling. {REFER TO ATTACHMENTS FOR EVIDENCE OF FINDINGS AND MEASUREMENTS BELOW) - Rated airflow: 5720 m3/h > 1,380 CFM > 1.59 m3/s - Unit operating at 50 Hz out of 60 Hz (83.3% of its maximum operation). - 83% * 1.58 m3/s = 1.31 m3/s - PSYCHOMETRIC CALCULATIONS: READINGS AT Pre-coil Temp & % RH: 27.1 Celsius @ 23.8% RH: Dry-bulb(Input) 27.1 °C RH(Input) 23.8 % Humidity ratio 5.29 g/kg Enthalpy 40.8 kJ/kg Wet-bulb 14.7 °C Dew point 4.7 °C Specific volume 0.858 m³/kg Density 1.172 kg/m³ Vapor pressure 854 Pa READINGS AT Post-coil temp & %RH: 17.2 Celsius @ 40.3% RH: Dry-bulb(Input) 17.2 °C RH(Input) 40.3 % Humidity ratio 4.89 g/kg Enthalpy 29.7 kJ/kg Wet-bulb 10.2 °C Dew point 3.6 °C Specific volume 0.829 m³/kg Density 1.212 kg/m³ Vapor pressure 791 Pa Calculations: Total cooling = (1.31 m^3/s) * 1.2 kg/m^3 * (40.8 kj/kg - 29.7 kj/kg ) = 17.4 kW / 3.517 = 4.96 TR Sensible cooling = (1.31 m^3/s) * 1.2 kg/m^3 * (27.1 CELSIUS - 17.2 CELSIUS) = 15.56 kW / 3.517 = 4.43 TR Latent cooling = Total cooling - Sensible Cooling = 0.53 TR Summary of calculations: Total cooling load @ 50 Hz > 4.96 TR Sensible cooling load @ 50 Hz > 4.43 TR Latent cooling load @ 50 Hz > 0.53 TR - Unit is not performing according to the estimated rated nominal value of 10 TR (10TR = 3,380/350), @ 50 Hz out of 60 Hz and only 7 Amperes motor draw. - Airflow is restricted possibly from Volume dampers or return grilles/fans. - Possible diagnosis, pulley is running on 2 belts instead of total of 3 (shown attached below). Motor power not properly transferring power to fan shaft. - Unit to be repaired. - B

Technical Details

System
Mechanical
Category
Air Handling Unit
Manufacturer
Carrier
Model
39FD340
Serial Number
884962
Location
1st floor- ME ROOM

Documents

0

No documents attached.

Need to update this asset?

Sign in with your technician or administrator account. Your name and every changed field are added to the asset history.

Sign in to update