Air Handling Unit 5
Location
1st floor- ME ROOM
Status
Operational
Priority
P4 - Monitor
Condition grade 3
Fair
1
2
3
4
5
FINDINGS & RECOMMENDED ACTION
- Nominal rated estimated to be 18 TR based on ASHRAE's standard rule of thumb of 350-400 CFM/TR. TR = 6,229.3 CFM / 350 = 17.8 TR > 18 TR. {REFER TO ATTACHMENTS FOR EVIDENCE OF FINDINGS AND MEASUREMENTS BELOW) - Rated airflow: 10540 m3/h > 6,229.3 CFM. - Unit operating at 55 Hz out of 60 Hz (91.6% of its maximum operation). - Airflow = 91.6% * 6,229.3 CFM = 5,706 CFM (2.68 m^3/s) - PSYCHOMETRIC CALCULATIONS: READINGS AT Pre-coil Temp & % RH: 22.5 Celsius @ 32.3% RH: Dry-bulb(Input) 22.5 °C RH(Input) 32.3 % Humidity ratio 5.45 g/kg Enthalpy 36.5 kJ/kg Wet-bulb 13.0 °C Dew point 5.1 °C Specific volume 0.845 m³/kg Density 1.190 kg/m³ Vapor pressure 881 Pa READINGS AT Post-coil temp & %RH: 11.2 Celsius @ 61.2% RH: Dry-bulb(Input) 11.2 °C RH(Input) 61.2 % Humidity ratio 5.04 g/kg Enthalpy 24.0 kJ/kg Wet-bulb 7.6 °C Dew point 4.0 °C Specific volume 0.812 m³/kg Density 1.238 kg/m³ Vapor pressure 814 Pa Calculations: Total cooling = (2.68 m^3/s) * 1.2 kg/m^3 * (36.5 kj/kg - 24 kj/kg ) = 40.2 kW / 3.517 = 11.4 TR Sensible cooling = (2.68 m^3/s) * 1.2 kg/m^3 * (22.5 CELSIUS - 11.2 CELSIUS) = 36.3 kW / 3.517 = 10.3 TR Latent cooling = Total cooling - Sensible Cooling = 1.1 TR Surface coil temp > 2.7 Celsius, Dew point > 5.1 Celsius > Condensate forms. Summary of calculations: Total cooling load @ 55 Hz > 11.4 TR Sensible cooling load @ 55 Hz > 10.3 TR Latent cooling load @ 55 Hz > 1.1 TR - Unit operates at 55 Hz out of 60 Hz and estimated total cooling of 11.4 TR out of presumed 18 TR total cooling with 5 Amps of motor draw. - Estimated cooling capacity efficiency > 63% - Major difference in cooling capacity against manufacturer technical datasheet, despite the completely different conditions of both tests, AHU is recommended for repair.
Technical Details
- System
- Mechanical
- Category
- Air Handling Unit
- Manufacturer
- Carrier
- Model
- 39FD360
- Serial Number
- 881965
- Location
- 1st floor- ME ROOM
Documents
0No documents attached.
Need to update this asset?
Sign in with your technician or administrator account. Your name and every changed field are added to the asset history.
Sign in to update