Air Handling Unit 6
Location
1st floor- ME ROOM
Status
Operational
Priority
P4 - Monitor
Condition grade 2
Good
1
2
3
4
5
FINDINGS & RECOMMENDED ACTION
{REFER TO ATTACHMENTS FOR EVIDENCE OF FINDINGS AND MEASUREMENTS BELOW) - Rated airflow: 31450 m^3/h > 18,587 CFM. - Unit operating at 52 Hz out of 60 Hz (86% of its maximum operation). - 16,108 CFM (7.57 m^3/s) - PSYCHOMETRIC CALCULATIONS: READINGS AT Pre-coil Temp % RH: 25.8 Celsius @ 27.1 RH: Dry-bulb(Input) 25.8 °C RH(Input) 27.1 % Humidity ratio 5.58 g/kg Enthalpy 40.2 kJ/kg Wet-bulb 14.4 °C Dew point 5.5 °C Specific volume 0.854 m³/kg Density 1.177 kg/m³ Vapor pressure 901 Pa READINGS AT Post-coil temp %RH: 12.9 Celsius @ 57.1% RH: Dry-bulb(Input) 12.9 °C RH(Input) 57.1 % Humidity ratio 5.26 g/kg Enthalpy 26.3 kJ/kg Wet-bulb 8.7 °C Dew point 4.6 °C Specific volume 0.817 m³/kg Density 1.230 kg/m³ Vapor pressure 850 Pa Calculations: Total cooling = (7.57 m^3/s) * 1.2 kg/m^3 * (40.2 kj/kg - 26.3 kj/kg ) = 126.3 kW / 3.517 = 35.9 TR Sensible cooling = (7.57 m^3/s) * 1.2 kg/m^3 * (25.8 CELSIUS - 12.9 CELSIUS) = 117.2 kW / 3.517 = 33.3 TR Latent cooling = Total cooling - Sensible Cooling = 2.6 TR Summary: Knowing that the unit is supposed to achieve about 45 TR at 60 Hz, Total cooling load @ 52 Hz > 35.9 TR Sensible cooling load @ 52 Hz > 33.3 TR Latent cooling load @ 52 Hz > 2.6 TR FINDINGS:-Expected drainage condensate > Condensate forms at 4 Celsius coil surface temp. -Chilled water temp supply and return is not present on site and on BMS. (No test points). - Given there is no technical datasheet, the unit is performing perfectly @52 Hz achieving 35.9 TR based on 45 TR (as per operator and ASHRAE 350-400 CFM/TR standards). - The unit is in good condition.
Technical Details
- System
- Mechanical
- Category
- Air Handling Unit
- Manufacturer
- Carrier
- Model
- 39FD580
- Serial Number
- 881975
- Location
- 1st floor- ME ROOM
Documents
0No documents attached.
Need to update this asset?
Sign in with your technician or administrator account. Your name and every changed field are added to the asset history.
Sign in to update