Air Handling Unit 7

Location

1st floor- ME ROOM

Status

Operational

Priority

P4 - Monitor

Condition grade 3

Fair

1

2

3

4

5

FINDINGS & RECOMMENDED ACTION

- Nominal estimated capacity 26 TR based on ASHRAE's rule of thumb and 350 CFM/TR. - Unit operating at 16.9 Amps motor draw. - Unit is operating at 55 Hz out of 60 Hz. Airflow = 8,821.5 CFM * 91.6% = 8,080 CFM = 3.8 m^3/s {REFER TO ATTACHMENTS FOR EVIDENCE OF FINDINGS AND MEASUREMENTS BELOW) - Unit operating at 55 Hz out of 60 Hz (91.6% of its maximum operation). - 91.6% * 8,821.5 CFM = 8,080.5 CFM (3.8 m^3/s) - PSYCHOMETRIC CALCULATIONS: READINGS AT Pre-coil Temp & % RH; 30.4 Celsius @ 18.7% RH: Dry-bulb(Input) 30.4 °C RH(Input) 18.7 % Humidity ratio 5.03 g/kg Enthalpy 43.4 kJ/kg Wet-bulb 15.6 °C Dew point 4.0 °C Specific volume 0.867 m³/kg Density 1.159 kg/m³ Vapor pressure 812 Pa READINGS AT Post-coil temp & %RH; 14.2 Celsius @ 48.3% RH: Dry-bulb(Input) 14.2 °C RH(Input) 48.3 % Humidity ratio 4.84 g/kg Enthalpy 26.5 kJ/kg Wet-bulb 8.8 °C Dew point 3.4 °C Specific volume 0.820 m³/kg Density 1.225 kg/m³ Vapor pressure 782 Pa Calculations: Total cooling = (3.8 m^3/s) * 1.2 kg/m^3 * (43.4 kj/kg - 26.5 kj/kg ) = 77.1 kW / 3.517 = 21.9 TR TR Sensible cooling = (3.8 m^3/s) * 1.2 kg/m^3 * (30.4 CELSIUS - 14.2 CELSIUS) = 73.9 kW / 3.517 = 21.0 TR Latent cooling = Total cooling - Sensible Cooling = 0.9 TR - Surface coil temp > 4.1 Celsius...Dew point> 4 Celsius. Summary of calculations: Total cooling load @ 55 Hz > 21.9 TR Sensible cooling load @ 55 Hz > 21 TR Latent cooling load @ 55 Hz > 0.9 TR - Unit is cooling at 22 TR against estimated rating of 23.8 TR out of 26 TR (91.6% of 26 TR = 23.8 TR based on 50/60 Hz). - Motor blower is operating at 16.9 Amps (Below maximum rated). - Estimated cooling capacity efficiency ratio is 92.4% HOWEVER, Technical datasheet shows major difference against completely different operating conditions. - Cooling coil fins seem to be in good cooling condition despite its age. Air flow seems to be in good required rate.

Technical Details

System
Mechanical
Category
Air Handling Unit
Manufacturer
Carrier
Model
39FD460
Serial Number
881968
Location
1st floor- ME ROOM

Documents

0

No documents attached.

Need to update this asset?

Sign in with your technician or administrator account. Your name and every changed field are added to the asset history.

Sign in to update