Air Handling Unit 8
Location
2nd floor- ME ROOM
Status
Operational
Priority
P4 - Monitor
Condition grade 3
Fair
1
2
3
4
5
FINDINGS & RECOMMENDED ACTION
- Estimated Nominal cooling capacity of AHU is 27 TR based on ASHRAE's 350-400 CFM/TR (TR = 9,273 CFM / 350 = 26.5 > 27 TR). - Rated airflow = 15690 m3/h > 9,273 CFM > 4.36 m3/s - Unit is operating at 14.5 Amps out of 11 Amps rated motor (See attached image below). -Airflow; Unit operating at 55 Hz out of 60 Hz, 91.6% of 4.36 m3/s = 4.0 m3/s. - Unit is expected to achieve 24.7 TR (91.6% of 27 TR). {REFER TO ATTACHMENTS FOR EVIDENCE OF FINDINGS AND MEASUREMENTS BELOW) - Airflow = 4.0 m3/s - Unit operating at 55 Hz out of 60 Hz (91.6% of its maximum operation). - PSYCHOMETRIC CALCULATIONS: READINGS AT Pre-coil Temp & % RH; 25.5 Celsius @ 27.5% RH: Dry-bulb(Input) 25.5 °C RH(Input) 27.5 % Humidity ratio 5.56 g/kg Enthalpy 39.8 kJ/kg Wet-bulb 14.3 °C Dew point 5.4 °C Specific volume 0.854 m³/kg Density 1.178 kg/m³ Vapor pressure 898 Pa READINGS AT Post-coil temp & %RH; 12.7 Celsius @ 53.8% RH: Dry-bulb(Input) 12.7 °C RH(Input) 53.8 % Humidity ratio 4.89 g/kg Enthalpy 25.1 kJ/kg Wet-bulb 8.2 °C Dew point 3.6 °C Specific volume 0.816 m³/kg Density 1.231 kg/m³ Vapor pressure 790 Pa Calculations: Total cooling = (4.0 m^3/s) * 1.2 kg/m^3 * (39.8 kj/kg - 25.1 kj/kg ) = 70.56 kW / 3.517 = 20.1 TR Sensible cooling = (4 m^3/s) * 1.2 kg/m^3 * (25.5 CELSIUS - 12.7 CELSIUS) = 61.44 kW / 3.517 = 17.5 TR Latent cooling = Total cooling - Sensible Cooling = 2.6 TR - Unit is operating at estimated cooling capacity efficiency of 81.3% (20.1 TR / 24.7 TR) - Unit is in good condition but motor is drawing more amps than required at 55 Hertz of operation VFD control, OVER-CURRENT. Reasons: Excessive fan mechanical loading. Worn or tight bearings. Incorrect pulley ratio or fan speed. Electrical voltage imbalance or low voltage. Motor winding problems. VFD or control-related issues. One belt missing from pulley drive system - Retain and increase frequency of PPM for filters blockage and pressure drop.
Technical Details
- System
- Mechanical
- Category
- Air Handling Unit
- Manufacturer
- Carrier
- Model
- 39FD460
- Serial Number
- 881969
- Location
- 2nd floor- ME ROOM
Documents
0No documents attached.
Need to update this asset?
Sign in with your technician or administrator account. Your name and every changed field are added to the asset history.
Sign in to update