Air Handling Unit 9

Location

2nd floor- ME ROOM

Status

Operational

Priority

P4 - Monitor

Condition grade 3

Fair

1

2

3

4

5

FINDINGS & RECOMMENDED ACTION

- Airflow = 12,056 CFM - Nominal Cooling capacity estimated at 35 TR based on ASHRAE's 350-400 CFM/TR ( TR = 12,056 CFM / 350 TR ). - Unit is operating at 55 Hz out of 60 Hz, 91.6% of total 12,056 CFM = 11,043 CFM > 5.2 m3/s. - Unit is expected to achieve 32.06 TR at 55 Hz. - Unit is drawing 15.9 Amps out of 34.9 Amps rated at 55 Hz. (No motor overcurrent detected) {REFER TO ATTACHMENTS FOR EVIDENCE OF FINDINGS AND MEASUREMENTS BELOW) - PSYCHOMETRIC CALCULATIONS: READINGS AT Pre-coil Temp & % RH; 22.5 Celsius @ 34% RH: Dry-bulb(Input) 22.5 °C RH(Input) 34.0 % Humidity ratio 5.74 g/kg Enthalpy 37.2 kJ/kg Wet-bulb 13.3 °C Dew point 5.9 °C Specific volume 0.845 m³/kg Density 1.190 kg/m³ Vapor pressure 927 Pa READINGS AT Post-coil temp & %RH; 12 Celsius @ 60.9% RH: Dry-bulb(Input) 12.0 °C RH(Input) 60.9 % Humidity ratio 5.29 g/kg Enthalpy 25.4 kJ/kg Wet-bulb 8.3 °C Dew point 4.7 °C Specific volume 0.815 m³/kg Density 1.234 kg/m³ Vapor pressure 854 Pa Calculations: - Total cooling = (5.2 m^3/s) * 1.2 kg/m^3 * (37.2 kj/kg - 25.4 kj/kg ) = 73.6 kW / 3.517 = 20.9 TR - Sensible cooling = (5.2 m^3/s) * 1.2 kg/m^3 * (22.5 CELSIUS - 12 CELSIUS) = 65.52 kW / 3.517 = 18.6 TR - Latent cooling = Total cooling - Sensible Cooling = 2.3 TR Summary of calculations: Total cooling load @ 55 Hz > 20.9 TR Sensible cooling load @ 55 Hz > 18.6 TR Latent cooling load @ 55 Hz > 2.3 TR - Unit operating at 55 Hz out of 60 Hz, approximately 91.7% of rated frequency. - Estimated airflow approximately 11,051 CFM based on rated airflow and operating frequency. - Pre-coil temperature 22.5°C and post-coil temperature 12°C, achieving 10.5°C temperature reduction. - Estimated cooling capacity approximately 20.9 TR based on psychrometric calculations and estimated airflow. - Cooling temperature reduction is satisfactory; however, actual cooling capacity requires airflow measurement and comparison against manufacturer's coil performance data. - Dirty filters might be restricting appropriate airflow.

Technical Details

System
Mechanical
Category
Air Handling Unit
Manufacturer
Carrier
Model
39FD550
Serial Number
881971
Location
2nd floor- ME ROOM

Documents

0

No documents attached.

Need to update this asset?

Sign in with your technician or administrator account. Your name and every changed field are added to the asset history.

Sign in to update