Air Handling Unit 10
Location
2nd floor- ME ROOM
Status
Operational
Priority
P4 - Monitor
Condition grade 2
Good
1
2
3
4
5
FINDINGS & RECOMMENDED ACTION
- Unit airflow > 29760 m³/h > 8.26 m3/s > 17,579 CFM - Unit is operating at 30 Hz out of 60 Hz (50%), 8.26 m3/s * 50% = 4.13 m3/s - Unit's motor blower is drawing 18 Amps (No overcurrent). - Estimated cooling capacity nominal; TR = 17,579 CFM / 300 = 60 TR, (Also verified by operator). - Operating at 30 Hz > 50 * 50% > 25 TR expected capacity measured. - PSYCHOMETRIC CALCULATIONS: READINGS AT Pre-coil Temp & % RH; 31.7 Celsius @ 17.1% RH: Dry-bulb(Input) 31.7 °C RH(Input) 17.1 % Humidity ratio 4.95 g/kg Enthalpy 44.6 kJ/kg Wet-bulb 16.0 °C Dew point 3.8 °C Specific volume 0.870 m³/kg Density 1.154 kg/m³ Vapor pressure 800 Pa READINGS AT Post-coil temp & %RH; 12.7 Celsius @ 46.5% RH: Calculations: Total cooling = (4.13 m^3/s) * 1.2 kg/m^3 * (44.6 kj/kg - 23.4 kj/kg ) = 105.1 kW / 3.517 = 30.0 TR Sensible cooling = (4.13 m^3/s) * 1.2 kg/m^3 * (31.7 CELSIUS - 12.7 CELSIUS) = 94.2 kW / 3.517 = 26.8 TR Latent cooling = Total cooling - Sensible Cooling = 3.2 TR - Surface coil temp > 4 Celsius...Dew point> 3.8 Celsius Summary of calculations: Total cooling load @ 30 Hz > 30 TR Sensible cooling load @ 50 Hz > 26.8 TR Latent cooling load @ 50 Hz > 3.2 TR - Unit is set to be satisfactory.
Technical Details
- System
- Mechanical
- Category
- Air Handling Unit
- Manufacturer
- Carrier
- Model
- 39FD670
- Serial Number
- 881979
- Location
- 2nd floor- ME ROOM
Documents
0No documents attached.
Need to update this asset?
Sign in with your technician or administrator account. Your name and every changed field are added to the asset history.
Sign in to update