Air Handling Unit 11
Location
2nd floor- ME ROOM
Status
Operational
Priority
P3 - Routine
Condition grade 3
Fair
1
2
3
4
5
FINDINGS & RECOMMENDED ACTION
- Airflow > 22108 m³/h > 6.1 m3/s > 13,066 CFM - Operating at 50 Hz (83.3% of 6.1 m3/s = 5.1 m3/s ) - Unit's motor drawing 30 Amps out of 59 Rated (No overcurrent detected). - Estimated nominal based on ASHRAE and rated capacity nameplate > 40 TR - Expected to achieve around 33.2 TR at 50 Hz. - PSYCHOMETRIC CALCULATIONS: READINGS AT Pre-coil Temp & % RH; 28.9 Celsius @ 19.5% RH: Dry-bulb(Input) 28.9 °C RH(Input) 19.5 % Humidity ratio 4.81 g/kg Enthalpy 41.4 kJ/kg Wet-bulb 14.9 °C Dew point 3.4 °C Specific volume 0.862 m³/kg Density 1.165 kg/m³ Vapor pressure 777 Pa READINGS AT Post-coil temp & %RH; 17.7 Celsius @ 38.8% RH: Dry-bulb(Input) 17.7 °C RH(Input) 38.8 % Humidity ratio 4.86 g/kg Enthalpy 30.1 kJ/kg Wet-bulb 10.4 °C Dew point 3.5 °C Specific volume 0.830 m³/kg Density 1.210 kg/m³ Vapor pressure 786 Pa Calculations: Total cooling = (5.1 m^3/s) * 1.2 kg/m^3 * (41.4 kj/kg - 30.1 kj/kg ) = 69.2 kW / 3.517 = 19.7 TR Sensible cooling = (5.1 m^3/s) * 1.2 kg/m^3 * (28.9 CELSIUS - 17.7 CELSIUS) = 68.5 kW / 3.517 = 19.5 TR Latent cooling = Total cooling - Sensible Cooling = 0.2 TR Summary calculations: Summary of calculations: Total cooling load @ 50 Hz > 19.7 TR Sensible cooling load @ 50 Hz > 19.5 TR Latent cooling load @ 50 Hz > 0.2 TR - Unit is showing poor performance eve without verifying against technical datasheet. - Duct leakage found at 8.91 m/s (shown in images below).
Technical Details
- System
- Mechanical
- Category
- Air Handling Unit
- Manufacturer
- Carrier
- Model
- 39FD570
- Serial Number
- 881972
- Location
- 2nd floor- ME ROOM
Documents
0No documents attached.
Need to update this asset?
Sign in with your technician or administrator account. Your name and every changed field are added to the asset history.
Sign in to update