Air Handling Unit 12
Location
2nd floor- ME ROOM
Status
Operational
Priority
P4 - Monitor
Condition grade 3
Fair
1
2
3
4
5
FINDINGS & RECOMMENDED ACTION
- Airflow > 22108 m³/h > 6.1 m3/s > 13,066 CFM - Unit operating at 53 Hz out of 60 Hz (88.3%) - Estimated nominal cooling capacity based on ASHRAE's 350-400 CFM/TR > 13,066 CFM / 350 TR = 40 TR - Expected result at 88.3% of 40 TR > 35 TR - Estimated current airflow > 5.4 m3/s - PSYCHOMETRIC CALCULATIONS: - Unit's motor is drawing 20.1 Amps out of 59 Amps rated. (No overcurrent detecte), Suspected underperformance due to airflow restriction. READINGS AT Pre-coil Temp & % RH; 27.2 Celsius @ 30.3% RH: Dry-bulb(Input) 27.2 °C RH(Input) 30.3 % Humidity ratio 6.79 g/kg Enthalpy 44.7 kJ/kg Wet-bulb 16.0 °C Dew point 8.3 °C Specific volume 0.860 m³/kg Density 1.170 kg/m³ Vapor pressure 1094 Pa READINGS AT Post-coil temp & %RH’; 12.5 Celsius @ 69.6% RH: Dry-bulb(Input) 12.5 °C RH(Input) 69.6 % Humidity ratio 6.25 g/kg Enthalpy 28.4 kJ/kg Wet-bulb 9.6 °C Dew point 7.1 °C Specific volume 0.817 m³/kg Density 1.231 kg/m³ Vapor pressure 1009 Pa Calculations: Total cooling = (5.4 m^3/s) * 1.2 kg/m^3 * (44.7 kj/kg - 28.4 kj/kg ) = 105.6 kW / 3.517 = 30.0 TR Sensible cooling = (5.4 m^3/s) * 1.2 kg/m^3 * (27.2 CELSIUS - 12.5 CELSIUS) = 95.3 kW / 3.517 = 27.1 TR Latent cooling = Total cooling - Sensible Cooling = 2.9 TR Surface coil temp > 2.8 Celsius, Dew point > 8.3 Celsius. CONDENSATION FORMS - Unit is achieving expected estimated cooling capacity against the airflow of 11,537 CFM @53 Hz achieving 384 CFM/TR comfort range as per ASHRAE's rule of thumb. - Unit is expected to achieve the rated cooling performance at T3 ambient temperature in summer due to promising results.
Technical Details
- System
- Mechanical
- Category
- Air Handling Unit
- Manufacturer
- Carrier
- Model
- 39FD570
- Serial Number
- 881973
- Location
- 2nd floor- ME ROOM
Documents
0No documents attached.
Need to update this asset?
Sign in with your technician or administrator account. Your name and every changed field are added to the asset history.
Sign in to update