Air Handling Unit 13
Location
2nd floor- ME ROOM
Status
Operational
Priority
P4 - Monitor
Condition grade 2
Good
1
2
3
4
5
FINDINGS & RECOMMENDED ACTION
- Airflow > 13605 m³/h > 3.8 m3/s > 8,041 CFM - ESTIMATED Cooling capacity based on ASHRAE's 350-400 CFM/TR > TR = 8,041 CFM / 350 TR = 23 TR - Unit is operating at 55 Hz out of 60 Hz (91.6% of maximum operation capacity). - Actual estimated airflow > 91.6% * 3.8 m3/s > 3.48 m3/s - Unit is expected to achieve 21 TR (91.6% of estimated nominal cooling capacity of 23 TR). - PSYCHOMETRIC CALCULATIONS: READINGS AT Pre-coil Temp & % RH; 23.7 Celsius @ 38% RH: Dry-bulb(Input) 23.7 °C RH(Input) 38.0 % Humidity ratio 6.91 g/kg Enthalpy 41.4 kJ/kg Wet-bulb 14.9 °C Dew point 8.6 °C Specific volume 0.850 m³/kg Density 1.184 kg/m³ Vapor pressure 1114 Pa READINGS AT Post-coil temp & %RH’; 12 Celsius @ 76.2% RH: Dry-bulb(Input) 12.0 °C RH(Input) 76.2 % Humidity ratio 6.63 g/kg Enthalpy 28.8 kJ/kg Wet-bulb 9.8 °C Dew point 7.9 °C Specific volume 0.816 m³/kg Density 1.233 kg/m³ Vapor pressure 1069 Pa Calculations: Total cooling = (3.48 m^3/s) * 1.2 kg/m^3 * (41.4 kj/kg - 28.8 kj/kg ) = 52.6 kW / 3.517 = 15 TR Sensible cooling = (3.48 m^3/s) * 1.2 kg/m^3 * (23.7 CELSIUS - 12 CELSIUS) = 48.9 kW / 3.517 = 13.9 TR Latent cooling = Total cooling - Sensible Cooling = 1.1 TR Summary of calculations: Total cooling load @ 55 Hz > 15 TR Sensible cooling load @ 55 Hz > 13.9 TR Latent cooling load @ 55 Hz > 1.1 TR - Unit is showing overall good cooling performance - To compare actual nominal capacity as per technical datasheet against achieved 15 TR total cooling at 55 Hz. - One belt missing from the pulley drive system could alter cooling efficiency.
Technical Details
- System
- Mechanical
- Category
- Air Handling Unit
- Manufacturer
- Carrier
- Model
- 39FD460
- Serial Number
- 881970
- Location
- 2nd floor- ME ROOM
Documents
0No documents attached.
Need to update this asset?
Sign in with your technician or administrator account. Your name and every changed field are added to the asset history.
Sign in to update