Air Handling Unit 14
Location
2nd floor- ME ROOM
Status
Operational
Priority
P4 - Monitor
Condition grade 2
Good
1
2
3
4
5
FINDINGS & RECOMMENDED ACTION
- Airflow > 31460 m³/h > 8.74 m3/s > 18,593 CFM - Nominal estimated cooling capacity based on ASHRAE's 350-400 CFM/TR > TR = 18,593 CFM / 350 = 53 TR - Expected capacity roughly at 55 Hz (91.6% of 53 TR) = 48.5 TR - Estimated actual airflow roughly > 8.0 m3/s - PSYCHOMETRIC CALCULATIONS: READINGS AT Pre-coil Temp & % RH; 24.3 Celsius @ 36.2% RH: Dry-bulb(Input) 24.3 °C RH(Input) 36.2 % Humidity ratio 6.83 g/kg Enthalpy 41.8 kJ/kg Wet-bulb 15.0 °C Dew point 8.4 °C Specific volume 0.852 m³/kg Density 1.182 kg/m³ Vapor pressure 1100 Pa READINGS AT Post-coil temp & %RH’; 13 Celsius @ 71.1% RH: Dry-bulb(Input) 13.0 °C RH(Input) 71.1 % Humidity ratio 6.61 g/kg Enthalpy 29.8 kJ/kg Wet-bulb 10.2 °C Dew point 7.9 °C Specific volume 0.819 m³/kg Density 1.229 kg/m³ Vapor pressure 1065 Pa Calculations: Total cooling = (8.0 m^3/s) * 1.2 kg/m^3 * (41.8 kj/kg - 29.8 kj/kg ) = 115.2 kW / 3.517 = 32.8 TR Sensible cooling = (8 m^3/s) * 1.2 kg/m^3 * (24.3 CELSIUS - 13 CELSIUS) = 108.5 kW / 3.517 = 30.8 TR Latent cooling = Total cooling - Sensible Cooling = 2 TR Summary of calculations: Total cooling load @ 55 Hz > 32.8 TR Sensible cooling load @ 55 Hz > 30.8 TR Latent cooling load @ 55 Hz > 2 TR - Unit operating at 38.5 Amps against rated 59.3 A. (No overcurrent detected) Unit is showing satisfactory cooling performance under current operating conditions, achieving 11.3°C temperature reduction and approximately 32.8 TR estimated total cooling capacity. Estimated cooling performance ratio approximately 67.6% against preliminary expected capacity of 48.5 TR at 55 Hz. Actual cooling capacity to be compared against manufacturer's technical datasheet under corresponding operating conditions.
Technical Details
- System
- Mechanical
- Category
- Air Handling Unit
- Manufacturer
- Carrier
- Model
- 39FD670
- Serial Number
- 881980
- Location
- 2nd floor- ME ROOM
Documents
0No documents attached.
Need to update this asset?
Sign in with your technician or administrator account. Your name and every changed field are added to the asset history.
Sign in to update