AtharAssetAsset Record
ATH-000088Rawabi · CMR

Air Handling Unit 16

Location

3rd floor- ME ROOm

Status

Operational

Priority

P4 - Monitor

Condition grade 2

Good

1

2

3

4

5

FINDINGS & RECOMMENDED ACTION

- Airflow > 45918 m³/h > 12.8 m3/s > 27,138 CFM - Unit operating at 58 Hz out of 60 Hz (96.7% of maximum operation) - Estimated Nominal cooling capacity based on ASHRAE's 350-400 CFM/TR > TR = 27,138 CFM / 350 = 77.5 TR - Expected TR value at 58 Hz > 96.7% * 77.5 TR = 74.9 - Estimated Airflow @ 58 Hz > 12.4 m3/s - Unit's motor is drawing 74.6 Amps (No overcurrent detected). - PSYCHOMETRIC CALCULATIONS: READINGS AT Pre-coil Temp & % RH; 23.8 Celsius @ 35.7% RH: Dry-bulb(Input) 23.8 °C RH(Input) 35.7 % Humidity ratio 6.53 g/kg Enthalpy 40.6 kJ/kg Wet-bulb 14.6 °C Dew point 7.7 °C Specific volume 0.850 m³/kg Density 1.184 kg/m³ Vapor pressure 1053 Pa READINGS AT Post-coil temp & %RH; 12.5 Celsius @ 66.5% RH: Dry-bulb(Input) 12.5 °C RH(Input) 66.5 % Humidity ratio 5.97 g/kg Enthalpy 27.7 kJ/kg Wet-bulb 9.3 °C Dew point 6.4 °C Specific volume 0.817 m³/kg Density 1.231 kg/m³ Vapor pressure 964 Pa Calculations: Total cooling = (12.4 m^3/s) * 1.2 kg/m^3 * (40.6 kj/kg - 27.7 kj/kg ) = 192 kW / 3.517 = 54.6 TR Sensible cooling = (12.4 m^3/s) * 1.2 kg/m^3 * (23.8 CELSIUS - 12.5 CELSIUS) = 168.1 kW / 3.517 = 47.8 TR Latent cooling = Total cooling - Sensible Cooling = 6.8 TR Summary of calculations: Total cooling load @ 58 Hz > 54.6 TR Sensible cooling load @ 55 Hz > 47.8 TR Latent cooling load @ 50 Hz > 6.8 TR FINDINGS: Unit is showing satisfactory cooling performance under current operating conditions, achieving 11.3°C temperature reduction and approximately 54.6 TR estimated total cooling capacity. Estimated cooling performance ratio approximately 72.9% against preliminary expected capacity of 74.9 TR at 58 Hz. Actual cooling capacity to be compared against manufacturer's technical datasheet under corresponding operating conditions. - Overall satisfactory cooling performance of AHU

Technical Details

System
Mechanical
Category
Air Handling Unit
Manufacturer
Carrier
Model
39FD780
Serial Number
881982
Location
3rd floor- ME ROOm

Documents

0

No documents attached.

Need to update this asset?

Sign in with your technician or administrator account. Your name and every changed field are added to the asset history.

Sign in to update