Air Handling Unit 18

Location

3rd floor- ME ROOM

Status

Operational

Priority

P4 - Monitor

Condition grade 2

Good

1

2

3

4

5

FINDINGS & RECOMMENDED ACTION

- Unit is operating at 58 Hz. - Motor seems to be drawing 93 Amps out of 88 Rated - POSSIBLE OVERCURRENT DETECTED (To be verified nameplate unclear values). - Airflow > 45918 m³/h > 12.8 m3/s - Airflow @ 58 Hz > 12.3 m3/s - PSYCHOMETRIC CALCULATIONS: READINGS AT Pre-coil Temp & % RH; 23.7 Celsius @ 36% RH: Dry-bulb(Input) 23.7 °C RH(Input) 36.0 % Humidity ratio 6.55 g/kg Enthalpy 40.5 kJ/kg Wet-bulb 14.5 °C Dew point 7.8 °C Specific volume 0.850 m³/kg Density 1.184 kg/m³ Vapor pressure 1055 Pa READINGS AT Post-coil temp & %RH’; 11.7 Celsius @ 68.3% RH: Dry-bulb(Input) 11.7 °C RH(Input) 68.3 % Humidity ratio 5.82 g/kg Enthalpy 26.4 kJ/kg Wet-bulb 8.8 °C Dew point 6.1 °C Specific volume 0.814 m³/kg Density 1.235 kg/m³ Vapor pressure 939 Pa Calculations: Total cooling = (12.3 m^3/s) * 1.2 kg/m^3 * (40.5 kj/kg - 26.4 kj/kg ) = 208.1 kW / 3.517 = 59.2 TR Sensible cooling = (12.3 m^3/s) * 1.2 kg/m^3 * (23.7 CELSIUS - 11.7 CELSIUS) = 177.1 kW / 3.517 = 50.4 TR Latent cooling = Total cooling - Sensible Cooling = 8.8 TR Summary of calculations: Total cooling load @ 58 Hz > 59.2 TR Sensible cooling load @ 58 Hz > 50.4 TR Latent cooling load @ 58 Hz > 8.8 TR FINDINGS: AHU operating at 58 Hz, with estimated airflow of 12.3 m³/s. Pre-coil temperature recorded at 23.7°C and post-coil temperature at 11.7°C, achieving a temperature reduction of 12°C. Psychrometric calculations indicate a total cooling duty of approximately 59.2 TR, including 50.4 TR sensible cooling and 8.8 TR latent cooling. Cooling coil demonstrates satisfactory cooling operation under the measured site conditions. The calculated cooling duty differs from manufacturer's nominal capacity due to differences in actual operating and rated testing conditions. Blower motor drawing approximately 93 A against an apparent rated current of 88 A, indicating possible overcurrent of approximately 5.7%. Motor nameplate values require verification before confirming overload. Recommend verifying motor rated current, checking three-phase current balance, and inspecting blower mechanical components for possible excessive loading.

Technical Details

System
Mechanical
Category
Air Handling Unit
Manufacturer
Carrier
Model
39FD780
Serial Number
881985
Location
3rd floor- ME ROOM

Documents

0

No documents attached.

Need to update this asset?

Sign in with your technician or administrator account. Your name and every changed field are added to the asset history.

Sign in to update