ATH-000091Rawabi · CMR

Air Handling Unit 19

Location

3rd floor- ME ROOM

Status

Operational

Priority

P4 - Monitor

Condition grade 2

Good

1

2

3

4

5

FINDINGS & RECOMMENDED ACTION

- Airflow > 45918 m³/h > 12.8 > 27,138 CFM - Unit operating @ 59 Hz (98.3%) - Motor blower is drawing 84 A at full load against RATED 86.4 A (No overcurrent detected). - PSYCHOMETRIC CALCULATIONS: READINGS AT Pre-coil Temp & % RH; 23.4 Celsius @ 35.2% RH: Dry-bulb(Input) 23.4 °C RH(Input) 35.2 % Humidity ratio 6.28 g/kg Enthalpy 39.5 kJ/kg Wet-bulb 14.2 °C Dew point 7.2 °C Specific volume 0.849 m³/kg Density 1.186 kg/m³ Vapor pressure 1013 Pa READINGS AT Post-coil temp & %RH’; 12.5Celsius @ 64% RH: Dry-bulb(Input) 12.5 °C RH(Input) 64.0 % Humidity ratio 5.75 g/kg Enthalpy 27.1 kJ/kg Wet-bulb 9.1 °C Dew point 5.9 °C Specific volume 0.817 m³/kg Density 1.231 kg/m³ Vapor pressure 928 Pa Calculations: Total cooling = (12.6 m^3/s) * 1.2 kg/m^3 * (39.5 kj/kg - 27.1 kj/kg ) = 187.5 kW / 3.517 = 53 TR Sensible cooling = (12.6 m^3/s) * 1.2 kg/m^3 * 1.02 kj/kg K * (23.4 CELSIUS - 12.5 CELSIUS) = 168.1 kW / 3.517 = 47.8 TR Latent cooling = Total cooling - Sensible Cooling = 5.2 TR Summary of calculations: Total cooling load @ 59 Hz > 53 TR Sensible cooling load @ 59 Hz > 47.8 TR Latent cooling load @ 59 Hz > 5.2 TR SHR: 90.2% FINDINGS: AHU operating at 59 Hz (98.3% of reference frequency), with blower motor drawing 84 A against rated current of 86.4 A. No overcurrent detected. Pre-coil temperature recorded at 23.4°C and post-coil temperature at 12.5°C, achieving a temperature reduction of 10.9°C. Psychrometric calculations indicate a total cooling duty of approximately 53.3 TR, including 47.8 TR sensible cooling and 5.2 TR latent cooling. Humidity ratio decreased from 6.28 g/kg to 5.75 g/kg, indicating moisture removal across the cooling coil. Cooling coil demonstrates satisfactory cooling operation under the measured site conditions. The calculated cooling duty reflects actual operating conditions, which differ from manufacturer's rated testing conditions. No motor overcurrent detected during inspection.

Technical Details

System
Mechanical
Category
Air Handling Unit
Manufacturer
Carrier
Model
39FD780
Serial Number
881981
Location
3rd floor- ME ROOM

Documents

0

No documents attached.

Need to update this asset?

Sign in with your technician or administrator account. Your name and every changed field are added to the asset history.

Sign in to update