Air Handling Unit 20
Location
4th floor- ME ROOM
Status
Operational
Priority
P4 - Monitor
Condition grade 2
Good
1
2
3
4
5
FINDINGS & RECOMMENDED ACTION
- Airflow> 45918m³/h > 12.8 m3/s > 27,138 CFM - Unit is operating @ 58 Hz. (96.7% of maximum operation 60 Hz) - Actual airflow measured to be around 22,128 CFM - Blower motor is drawing 75.7 A out of 88 RATED (No overcurrent detected). - PSYCHOMETRIC CALCULATIONS: READINGS AT Pre-coil Temp & % RH; 24.3 Celsius @ 29.4% RH: Dry-bulb(Input) 24.3 °C RH(Input) 29.4 % Humidity ratio 5.53 g/kg Enthalpy 38.5 kJ/kg Wet-bulb 13.8 °C Dew point 5.3 °C Specific volume 0.850 m³/kg Density 1.183 kg/m³ Vapor pressure 894 Pa READINGS AT Post-coil temp & %RH’; 12.5 Celsius @ 56.2% RH: Dry-bulb(Input) 12.5 °C RH(Input) 56.2 % Humidity ratio 5.04 g/kg Enthalpy 25.3 kJ/kg Wet-bulb 8.3 °C Dew point 4.0 °C Specific volume 0.816 m³/kg Density 1.232 kg/m³ Vapor pressure 815 Pa Calculations: Total cooling = (10.4 m^3/s) * 1.2 kg/m^3 * (38.5 kj/kg - 25.3 kj/kg ) = 164.7 kW / 3.517 = 46.8 TR Sensible cooling = (10.4 m^3/s) * 1.2 kg/m^3 * 1.02 kj/kg K * (24.3 CELSIUS - 12.5 CELSIUS) = 150.2 kW / 3.517 = 42.7 TR Latent cooling = Total cooling - Sensible Cooling = 4.1 TR Summary of calculations: Total cooling load @ 58 Hz > 46.8 TR Sensible cooling load @ 58 Hz > 42.7 TR Latent cooling load @ 58 Hz > 4.1 TR SHR: 0.91 AHU operating at 58 Hz (96.7% of reference frequency), with actual airflow measured at approximately 22,128 CFM. Pre-coil temperature recorded at 24.3°C and post-coil temperature at 12.5°C, achieving a temperature reduction of 11.8°C. Psychrometric calculations indicate a total cooling duty of approximately 46.8 TR, including 42.7 TR sensible cooling and 4.1 TR latent cooling. Cooling coil demonstrates satisfactory cooling operation under the measured site conditions. The calculated cooling duty reflects the actual operating conditions, which differ from the manufacturer's rated testing conditions. Actual measured airflow is approximately 81.5% of rated.
Technical Details
- System
- Mechanical
- Category
- Air Handling Unit
- Manufacturer
- Carrier
- Model
- 39FD780
- Serial Number
- 881986
- Location
- 4th floor- ME ROOM
Documents
0No documents attached.
Need to update this asset?
Sign in with your technician or administrator account. Your name and every changed field are added to the asset history.
Sign in to update