Air Handling Unit 21
Location
Next to mosque -ME ROOM
Status
Operational
Priority
P4 - Monitor
Condition grade 3
Fair
1
2
3
4
5
FINDINGS & RECOMMENDED ACTION
- Unit is operating at 55 Hertz. - Airflow > 8500 m³/h > 2.36 m³/s > 5021 CFM - Actual airflow > 4490 CFM > 2.1 m³/s - PSYCHOMETRIC CALCULATIONS: READINGS AT Pre-coil Temp & % RH; 25.2 Celsius @ 25% RH: Dry-bulb(Input) 25.2 °C RH(Input) 25.0 % Humidity ratio 4.96 g/kg Enthalpy 38.0 kJ/kg Wet-bulb 13.6 °C Dew point 3.8 °C Specific volume 0.852 m³/kg Density 1.180 kg/m³ Vapor pressure 802 Pa READINGS AT Post-coil temp & %RH’; 14.9 Celsius @ 43.7% RH: Dry-bulb(Input) 14.9 °C RH(Input) 43.7 % Humidity ratio 4.58 g/kg Enthalpy 26.6 kJ/kg Wet-bulb 8.8 °C Dew point 2.7 °C Specific volume 0.822 m³/kg Density 1.222 kg/m³ Vapor pressure 740 Pa Calculations: Total cooling = (2.1 m^3/s) * 1.2 kg/m^3 * (38 kj/kg - 26.6 kj/kg ) = 28.7 kW / 3.517 = 8.2 TR Sensible cooling = (2.1 m^3/s) * 1.2 kg/m^3 * (25.2 CELSIUS - 14.9 CELSIUS) = 26.0 kW / 3.517 = 7.4 TR Latent cooling = Total cooling - Sensible Cooling = 0.8 TR FINDINGS: 4,468 CFM / 8.2 TR = 544.9 CFM/TR 544.9 CFM/TR is quite high and above the comfort ASHRAE rule of thumb of 350-400 CFM/TR - Unit is suspected to have lost its design performance of cooling along other defect components such as belt drive system and heaters.
Technical Details
- System
- Mechanical
- Category
- Air Handling Unit
- Manufacturer
- Carrier
- Model
- 39FD350
- Serial Number
- 881963
- Location
- Next to mosque -ME ROOM
Documents
0No documents attached.
Need to update this asset?
Sign in with your technician or administrator account. Your name and every changed field are added to the asset history.
Sign in to update