Air Handling Unit 22
Location
Next to mosque -ME ROOM
Status
Operational
Priority
P4 - Monitor
Condition grade 4
Poor
1
2
3
4
5
FINDINGS & RECOMMENDED ACTION
- Unit is operating at 58 Hz - Blower motor drawing 5.4 A against rated 5.1 ( OVERCURRENT DETECTED) - Airflow > 8500 m³/h > 2.36 m³/s > 5,201 - Actual airflow > 4800 CFM > 2.3 m³/s - PSYCHOMETRIC CALCULATIONS: READINGS AT Pre-coil Temp & % RH; 20.4 Celsius @ 37.2% RH: Dry-bulb(Input) 20.4 °C RH(Input) 37.2 % Humidity ratio 5.52 g/kg Enthalpy 34.5 kJ/kg Wet-bulb 12.2 °C Dew point 5.3 °C Specific volume 0.839 m³/kg Density 1.199 kg/m³ Vapor pressure 892 Pa READINGS AT Post-coil temp & %RH’; 13.3 Celsius @ 59.7% RH: Dry-bulb(Input) 13.3 °C RH(Input) 59.7 % Humidity ratio 5.65 g/kg Enthalpy 27.6 kJ/kg Wet-bulb 9.3 °C Dew point 5.6 °C Specific volume 0.819 m³/kg Density 1.228 kg/m³ Vapor pressure 912 Pa Calculations: Total cooling = (2.3 m³/s) * 1.2 kg/m³ * (34.5 kj/kg - 27.6 kj/kg ) = 19.0 kW / 3.517 = 5.4 TR Sensible cooling = 5.4 TR Latent cooling = Total cooling - Sensible Cooling = 0 TR Unit is critically defect at 906 CFM/TR performance. Urgent verification is required otherwise plan replacement immediately.
Technical Details
- System
- Mechanical
- Category
- Air Handling Unit
- Manufacturer
- Carrier
- Model
- 39FD350
- Serial Number
- 881964
- Location
- Next to mosque -ME ROOM