AtharAssetAsset Record
ATH-000095Rawabi · CMR

Air Handling Unit 23

Location

1ST FLOOR ROOF

Status

Operational

Priority

P3 - Routine

Condition grade 4

Poor

1

2

3

4

5

FINDINGS & RECOMMENDED ACTION

- Airflow > 23139 m³/h > 6.4 m³/s > 13,676 CFM - Actual airflow > 9,340 CFM > 4.4 m3/s @ 52 Hz - PSYCHOMETRIC CALCULATIONS: READINGS AT Pre-coil Temp & % RH; 28 Celsius @ 21.1% RH: Dry-bulb(Input) 21.1 °C RH(Input) 28.0 % Humidity ratio 4.33 g/kg Enthalpy 32.2 kJ/kg Wet-bulb 11.3 °C Dew point 1.9 °C Specific volume 0.839 m³/kg Density 1.197 kg/m³ Vapor pressure 701 Pa READINGS AT Post-coil temp & %RH’; 17.4 Celsius @ 37.9% RH Dry-bulb(Input) 17.4 °C RH(Input) 37.9 % Humidity ratio 4.66 g/kg Enthalpy 29.3 kJ/kg Wet-bulb 10.1 °C Dew point 2.9 °C Specific volume 0.829 m³/kg Density 1.212 kg/m³ Vapor pressure 753 Pa Calculations: Total cooling = (4.4 m³/s) * 1.2 kg/m³ * (32.2 kj/kg - 29.3 kj/kg ) = 15.3 kW / 3.517 = 4.35 TR Sensible cooling = (4.4 m³/s) * 1.2 kg/m³ * (28 CELSIUS - 17.4 CELSIUS) = 19 kW / 3.517 = 5.4 TR Latent cooling = Total cooling - Sensible Cooling = 0 TR Test has been done more than once to confirm AHU to be defect cooling performance - Unit is passed its life expectancy and is time for replacement due to loss of total cooling performance.

Technical Details

System
Mechanical
Category
Air Handling Unit
Manufacturer
Carrier
Model
39FD570
Serial Number
881974
Location
1ST FLOOR ROOF

Documents

0

No documents attached.