AtharAssetAsset Record
ATH-000096Rawabi · CMR

Air Handling Unit 24

Location

Basement - ME eq ROOM

Status

Operational

Priority

P2 - Planned

Condition grade 4

Poor

1

2

3

4

5

FINDINGS & RECOMMENDED ACTION

- Airflow > 10200 m³/h > 2.83 m³/s > 6,029 CFM - Unit operating at 52 Hz - Blower motor drawing 3.3 A (No overcurrent detected) - Actual airflow > 4,823 CFM > 2.27 m³/s - PSYCHOMETRIC CALCULATIONS: READINGS AT Pre-coil Temp & % RH; 20.9 Celsius @ 37.9% RH: Dry-bulb(Input) 20.9 °C RH(Input) 37.9 % Humidity ratio 5.81 g/kg Enthalpy 35.8 kJ/kg Wet-bulb 12.7 °C Dew point 6.0 °C Specific volume 0.841 m³/kg Density 1.196 kg/m³ Vapor pressure 937 Pa READINGS AT Post-coil temp & %RH’; 15.1 Celsius @ 51.1% RH: Dry-bulb(Input) 15.1 °C RH(Input) 51.1 % Humidity ratio 5.43 g/kg Enthalpy 28.9 kJ/kg Wet-bulb 9.9 °C Dew point 5.1 °C Specific volume 0.824 m³/kg Density 1.221 kg/m³ Vapor pressure 877 Pa Calculations: Total cooling = (2.27 m³/s) * 1.2 kg/m³ * (35.8 kj/kg - 28.9 kj/kg ) = 18.8 kW / 3.517 = 5.34 TR Sensible cooling = (2.27 m³/s) * 1.2 kg/m³ * 1.02 kj/kg K ( 20.9 CELSIUS - 15.1 CELSIUS) = 16.1 kW / 3.517 = 4.58 TR Latent cooling = Total cooling - Sensible Cooling = 0.76 TR Summary of calculations: Total cooling load @ 52 Hz > 5.34 TR Sensible cooling load @ 52 Hz > 4.58 TR Latent cooling load @ 52 Hz > 0.76 TR - Unit is providing 911 CFM / TR (out of 350-400 CFM/TR comfort range recommended) - Unit is suspected to be underperforming and overage since 1886. Unit operating at 52 Hz, with estimated airflow of 4,823 CFM compared to rated airflow of 6,029 CFM. Pre-coil temperature recorded at 20.9°C and post-coil temperature at 15.1°C, achieving a temperature reduction of 5.8°C. Estimated total cooling capacity approximately 5.34 TR, including 4.58 TR sensible and 0.76 TR latent cooling. Estimated operating airflow-to-cooling ratio approximately 903 CFM/TR, higher than typical comfort-cooling design ratios. Cooling capacity appears relatively low for the unit's airflow; however, entering-air conditions are already cool and relatively dry. Further investigation recommended to verify airflow, chilled-water flow, cooling coil condition and control valve operation before confirming underperformance.

Technical Details

System
Mechanical
Category
Air Handling Unit
Manufacturer
Carrier
Model
39FD450
Serial Number
881966
Location
Basement - ME eq ROOM

Documents

0

No documents attached.

Need to update this asset?

Sign in with your technician or administrator account. Your name and every changed field are added to the asset history.

Sign in to update