Air Handling Unit 25
Location
Basement - ME ROOM
Status
Operational
Priority
P2 - Planned
Condition grade 3
Fair
1
2
3
4
5
FINDINGS & RECOMMENDED ACTION
- Rated Airflow > 10200 m³/h > 2.83 m³/s > 6,028 CFM - PSYCHOMETRIC CALCULATIONS: READINGS AT Pre-coil Temp & % RH; 22.7 Celsius @ 30.8% RH: Dry-bulb(Input) 22.7 °C RH(Input) 30.8 % Humidity ratio 5.26 g/kg Enthalpy 36.2 kJ/kg Wet-bulb 12.9 °C Dew point 4.6 °C Specific volume 0.845 m³/kg Density 1.189 kg/m³ Vapor pressure 850 Pa READINGS AT Post-coil temp & %RH’; 17.9 Celsius @ 38.6% RH: Dry-bulb(Input) 17.9 °C RH(Input) 38.6 % Humidity ratio 4.90 g/kg Enthalpy 30.4 kJ/kg Wet-bulb 10.5 °C Dew point 3.6 °C Specific volume 0.831 m³/kg Density 1.209 kg/m³ Vapor pressure 792 Pa Summary of calculations: Total cooling load @ 50 Hz > 4.95 TR Sensible cooling load @ 50 Hz > 4.18 TR Latent cooling load @ 50 Hz > 0.77 TR - Unit is suspected to be underperforming - Unit has passed its life expectancy so replacement is definitely recommended with respect to its current poor performance despite missing technical datasheet condition comparison.
Technical Details
- System
- Mechanical
- Category
- Air Handling Unit
- Manufacturer
- Carrier
- Model
- 39FD450
- Serial Number
- 881967
- Location
- Basement - ME ROOM