AtharAssetAsset Record
ATH-000097Rawabi · CMR

Air Handling Unit 25

Location

Basement - ME ROOM

Status

Operational

Priority

P2 - Planned

Condition grade 3

Fair

1

2

3

4

5

FINDINGS & RECOMMENDED ACTION

- Rated Airflow > 10200 m³/h > 2.83 m³/s > 6,028 CFM - PSYCHOMETRIC CALCULATIONS: READINGS AT Pre-coil Temp & % RH; 22.7 Celsius @ 30.8% RH: Dry-bulb(Input) 22.7 °C RH(Input) 30.8 % Humidity ratio 5.26 g/kg Enthalpy 36.2 kJ/kg Wet-bulb 12.9 °C Dew point 4.6 °C Specific volume 0.845 m³/kg Density 1.189 kg/m³ Vapor pressure 850 Pa READINGS AT Post-coil temp & %RH’; 17.9 Celsius @ 38.6% RH: Dry-bulb(Input) 17.9 °C RH(Input) 38.6 % Humidity ratio 4.90 g/kg Enthalpy 30.4 kJ/kg Wet-bulb 10.5 °C Dew point 3.6 °C Specific volume 0.831 m³/kg Density 1.209 kg/m³ Vapor pressure 792 Pa Summary of calculations: Total cooling load @ 50 Hz > 4.95 TR Sensible cooling load @ 50 Hz > 4.18 TR Latent cooling load @ 50 Hz > 0.77 TR - Unit is suspected to be underperforming - Unit has passed its life expectancy so replacement is definitely recommended with respect to its current poor performance despite missing technical datasheet condition comparison.

Technical Details

System
Mechanical
Category
Air Handling Unit
Manufacturer
Carrier
Model
39FD450
Serial Number
881967
Location
Basement - ME ROOM

Documents

0

No documents attached.