AtharAssetAsset Record
ATH-000098Rawabi · CMR

Air Handling Unit 26

Location

HeliPad

Status

Partially Operational

Priority

P2 - Planned

Condition grade 4

Poor

1

2

3

4

5

FINDINGS & RECOMMENDED ACTION

- Airflow > 9154 m³/h > 2.5 m3/s - Actual estimated airflow > (3269 RPM / 3500 RPM) * 2.5 m3/s = 2.37 m3/s - Unit is operating at 55 Hz - Blower motor drawing 2.0 A (No overcurrent detected). - PSYCHOMETRIC CALCULATIONS: READINGS AT Pre-coil Temp & % RH; 28.3 Celsius @ 25.2% RH: Dry-bulb(Input) 28.3 °C RH(Input) 25.2 % Humidity ratio 6.01 g/kg Enthalpy 43.8 kJ/kg Wet-bulb 15.8 °C Dew point 6.5 °C Specific volume 0.862 m³/kg Density 1.167 kg/m³ Vapor pressure 970 Pa READINGS AT Post-coil temp & %RH’; 17.7 Celsius @ 43.3% RH: Dry-bulb(Input) 17.7 °C RH(Input) 43.3 % Humidity ratio 5.43 g/kg Enthalpy 31.6 kJ/kg Wet-bulb 11.0 °C Dew point 5.1 °C Specific volume 0.831 m³/kg Density 1.210 kg/m³ Vapor pressure 877 Pa Calculations: Total cooling = (2.37 m^3/s) * 1.2 kg/m^3 * (43.8 kj/kg - 31.6 kj/kg ) = 34.7 kW / 3.517 = 10 TR Sensible cooling = (2.37 m^3/s) * 1.2 kg/m^3 * (28.3 CELSIUS - 17.7 CELSIUS) = 30.1 kW / 3.517 = 8.6 TR Latent cooling = Total cooling - Sensible Cooling = 1.4 TR Summary of calculations: Total cooling load @ 55 Hz > 10 TR Sensible cooling load @ 55 Hz > 8.6 TR Latent cooling load @ 55 Hz > 1.4 TR AHU operating at 55 Hz, with blower motor drawing 2.0 A and no overcurrent detected. Pre-coil temperature recorded at 28.3°C and post-coil temperature at 17.7°C, achieving a temperature reduction of 10.6°C. Calculated cooling duty is approximately 10 TR under the recorded operating conditions. Leaving-air temperature of 17.7°C is relatively high and requires verification against the AHU design requirements. Cooling coil surface temperature recorded at 9°C, above the entering-air dew point of 6.5°C, with no visible condensate observed. Psychrometric calculations indicate minor moisture removal, but actual condensation was not confirmed. Prior to checking chilled-water supply and return temperatures, water flow, control-valve operation and coil cleanliness to assess cooling performance.

Technical Details

System
Mechanical
Category
Air Handling Unit
Manufacturer
Carrier
Model
39FD7340
Serial Number
882518
Location
HeliPad

Documents

0

No documents attached.

Need to update this asset?

Sign in with your technician or administrator account. Your name and every changed field are added to the asset history.

Sign in to update