Air Handling Unit 27
Location
HeliPad
Status
Operational
Priority
P2 - Planned
Condition grade 4
Poor
1
2
3
4
5
FINDINGS & RECOMMENDED ACTION
- Unit is operating at 55 Hz - Airflow > 18993 m³/h > 5.28 m³/s > 11,234 CFM - Estimated actual airflow > 5.28 m³/s * (1631/1740) = 4.9 m³/s - Actual external static pressure: 0.13 kPa - (-0.13 kPa) = 260 Pa - Blower motor drawing 7.5 A agaisnt rated 15.4 A (No overcurrent detected). - PSYCHOMETRIC CALCULATIONS: READINGS AT Pre-coil Temp & % RH; 29.2 Celsius @ 23.7% RH: Dry-bulb(Input) 29.2 °C RH(Input) 23.7 % Humidity ratio 5.96 g/kg Enthalpy 44.6 kJ/kg Wet-bulb 16.0 °C Dew point 6.4 °C Specific volume 0.865 m³/kg Density 1.163 kg/m³ Vapor pressure 961 Pa READINGS AT Post-coil temp & %RH’; 18.4 Celsius @ 42.1% RH: Dry-bulb(Input) 18.4 °C RH(Input) 42.1 % Humidity ratio 5.52 g/kg Enthalpy 32.5 kJ/kg Wet-bulb 11.4 °C Dew point 5.3 °C Specific volume 0.833 m³/kg Density 1.207 kg/m³ Vapor pressure 891 Pa Calculations: Total cooling = (4.9 m³/s) * 1.2 kg/m³ * (44,6 kj/kg - 32.5 kj/kg ) = 71.1 kW / 3.517 = 20.2 TR Sensible cooling = (4.9 m³/s) * 1.2 kg/m³ * (29.2 CELSIUS - 18.4 CELSIUS) = 63.5 kW / 3.517 = 18.1 TR Latent cooling = Total cooling - Sensible Cooling = 2.1 TR Summary of calculations: Total cooling load @ 55 Hz > 20.2 TR Sensible cooling load @ 55 Hz > 18.1 TR Latent cooling load @ 55 Hz > 2.1 TR FINDINGS: - Unit is currently operating at 516 CFM/TR which is out of ASHRAE's recommended comfort range of 350-400 CFM/TR. - Unit is suspected to be underperforming and may not be able to achieve design cooling performance under technical datasheet conditions.
Technical Details
- System
- Mechanical
- Category
- Air Handling Unit
- Manufacturer
- Carrier
- Model
- 39FD470
- Serial Number
- 882519
- Location
- HeliPad
Documents
0No documents attached.
Need to update this asset?
Sign in with your technician or administrator account. Your name and every changed field are added to the asset history.
Sign in to update