Air Handling Unit 28
Location
M.R.I
Status
Operational
Priority
P3 - Routine
Condition grade 3
Fair
1
2
3
4
5
FINDINGS & RECOMMENDED ACTION
- Unit is operating at 45 Hz. - Rated Airflow > 10200 m³/h > 2.83 m³/s > 6,028 CFM - Airflow @45 Hz > 2.1 m³/s - Blower motor is drawing 7.4 A (No overcurrent detected) - PSYCHOMETRIC CALCULATIONS: READINGS AT Pre-coil Temp & % RH; 21.7 Celsius @ 35.6% RH: Dry-bulb(Input) 21.7 °C RH(Input) 35.6 % Humidity ratio 5.73 g/kg Enthalpy 36.4 kJ/kg Wet-bulb 13.0 °C Dew point 5.8 °C Specific volume 0.843 m³/kg Density 1.193 kg/m³ Vapor pressure 924 Pa READINGS AT Post-coil temp & %RH’; 12.9 Celsius @ 60.1% RH: Dry-bulb(Input) 12.9 °C RH(Input) 60.1 % Humidity ratio 5.54 g/kg Enthalpy 27.0 kJ/kg Wet-bulb 9.0 °C Dew point 5.4 °C Specific volume 0.818 m³/kg Density 1.230 kg/m³ Vapor pressure 894 Pa Calculations: Total cooling = (2.1 m³/s) * 1.2 kg/m³ * (36.4 kj/kg - 27 kj/kg) = 23.7 kW / 3.517 = 6.7 TR Sensible cooling = (2.1 m³/s) * 1.2 kg/m³ * 1.02 kj/kg K * (21.7 CELSIUS - 12.9 CELSIUS) = 22.6 kW / 3.517 = 6.4 TR Latent cooling = Total cooling - Sensible Cooling = 0.3 TR Summary of calculations: Total cooling load @45 Hz > 6.7 TR Sensible cooling load @ 45 Hz > 6.4 TR Latent cooling load @ 45 Hz > 0.3 TR - SHR = 95.5% - Unit is sensible dominant at 45 Hertz and current operating conditions. - Unit is suspected to be underperforming - Another assessment shall be done on the chilled water supply and return to verify cooling coil defect or starvation.
Technical Details
- System
- Mechanical
- Category
- Air Handling Unit
- Manufacturer
- Carrier
- Model
- 39FD450
- Serial Number
- 891083
- Location
- M.R.I
Documents
0No documents attached.
Need to update this asset?
Sign in with your technician or administrator account. Your name and every changed field are added to the asset history.
Sign in to update