AtharAssetAsset Record
ATH-000101Rawabi · CMR

Air-Cooled Chiller 1

Location

Roof Chiller Yard

Status

Operational

Priority

P3 - Routine

Condition grade 3

Fair

1

2

3

4

5

FINDINGS & RECOMMENDED ACTION

Chiller visually inspected and found in generally acceptible external condition. Electrical current measured at approximately 165 A, with no overcurrent indications observed during operation. Chilled water pipe surface tempratures recorded at 14.6°C and 17.6°C, giving an approximate temprature differance of 3.0°C despite thermal gun usage and error possibilites. Chilled water tempratures are relatively high compared to typical cooling operating conditions. Electronic expansion valve controller is powered and displaying 4.7, with charge indicator illuminated. Minor surface corrosion and rusting observed around pipe flanges and exposed fittings. FINDINGS: Chiller is operational, however the measured chilled water tempratures indicate reduced cooling performace under the recorded operating conditions. Overall external condition is acceptible, with localized corrosion requiring maintanance.

Technical Details

System
Mechanical
Category
Chiller
Manufacturer
Zamil
Model
ASC300B
Serial Number
HEABZ0001M
Location
Roof Chiller Yard

Documents

0

No documents attached.