Air-Cooled Chiller 3

Status

Operational

Priority

P3 - Routine

Condition grade 4

Poor

1

2

3

4

5

FINDINGS & RECOMMENDED ACTION

Chiller visually inspected and found in generally acceptible external condition. Electrical current measured at approximately 307 A, with no overcurrent indications compared to the unit's maximum operating current protection rating of 1,000 A. Chilled water pipe surface tempratures recorded at 11.1°C and 9.6°C, giving a temprature differance of 1.5°C. Chilled water pressure gauges indicate approximately 4–5 bar, with no significant pressure differance observed. Chilled water tempratures are relativly high, with low temprature differance indicating limited heat removal under the recorded operating conditions. Surface corrosion observed around pipe flanges, pressure gauge connections and exposed fittings FINDINGS: Chiller is producing chilled water, but the measured tempratures and low temperature differance indicate reduced cooling performace under the recorded conditions. Overall external condition is acceptible, with localized corrosion requiring maintanance.

Technical Details

System
Mechanical
Category
Chiller
Manufacturer
Zamil
Model
ASC300B
Serial Number
HSA101-00180799
Location
—

Documents

0

No documents attached.