AtharAssetAsset Record
ATH-000104Rawabi · CMR

Air-Cooled Chiller 4

Status

Operational

Priority

P3 - Routine

Condition grade 4

Poor

1

2

3

4

5

FINDINGS & RECOMMENDED ACTION

Chiller visually inspected and found in generally good external condition. Electrical panel, circuit brreakers, contactors and wiring appear in good condition, with no visible signs of overheating. Electrical current recorded at approximately 340 A, below the unit's rated minimum circuit ampacity of 818.24 A. This reading does not indicate an ovrcurrent condition. chilled water piping surface temperatures recorded at 13.7°C and 15.1°C, giving a temperature difference of 1.4°C. Water pressure gauge indicates approximately 5 bar. Electronic expansion valve controller is powered, with the charge indicator illuminated. Minor surface corrosion observed around pressure gauge connections and exposed piping.

Technical Details

System
Mechanical
Category
Chiller
Manufacturer
Zamil
Model
ASC300B
Serial Number
HSA101-00180801
Location
—

Documents

0

No documents attached.

Need to update this asset?

Sign in with your technician or administrator account. Your name and every changed field are added to the asset history.