Air-Cooled Chiller 4
Status
Operational
Priority
P3 - Routine
Condition grade 4
Poor
1
2
3
4
5
FINDINGS & RECOMMENDED ACTION
Chiller visually inspected and found in generally good external condition. Electrical panel, circuit brreakers, contactors and wiring appear in good condition, with no visible signs of overheating. Electrical current recorded at approximately 340 A, below the unit's rated minimum circuit ampacity of 818.24 A. This reading does not indicate an ovrcurrent condition. chilled water piping surface temperatures recorded at 13.7°C and 15.1°C, giving a temperature difference of 1.4°C. Water pressure gauge indicates approximately 5 bar. Electronic expansion valve controller is powered, with the charge indicator illuminated. Minor surface corrosion observed around pressure gauge connections and exposed piping.
Technical Details
- System
- Mechanical
- Category
- Chiller
- Manufacturer
- Zamil
- Model
- ASC300B
- Serial Number
- HSA101-00180801
- Location
- —
Documents
0No documents attached.