ATH-000105Rawabi · CMR

Air-Cooled Chiller 5

Status

Operational

Priority

P3 - Routine

Condition grade 3

Fair

1

2

3

4

5

FINDINGS & RECOMMENDED ACTION

Chiller visually inspected and found in generally good external condition. Electrical current readings recorded at 13.7 A and 10.9 A on the inspected circuits, with no obvious abnormality indicated. Chilled-water pipe temperatures recorded at 7.8°C and 9.7°C, giving a temperature difference of 1.9°C. Chilled-water pressure gauges indicate approximately 4.5–5.0 bar, with no significant pressure difference observed. FINDINGS: Chiller is producing chilled water, with a measured temperature difference of 1.9°C. The relatively low temperature difference may indicate low cooling demand during operation. Overall visual condition is good, with no major external defects identified. Minor surface corrosion observed around pressure gauge connections and exposed piping. Electrical components appear visually intact.