Air-Cooled Chiller 5
Status
Operational
Priority
P3 - Routine
Condition grade 3
Fair
1
2
3
4
5
FINDINGS & RECOMMENDED ACTION
Chiller visually inspected and found in generally good external condition. Electrical current readings recorded at 13.7 A and 10.9 A on the inspected circuits, with no obvious abnormality indicated. Chilled-water pipe temperatures recorded at 7.8°C and 9.7°C, giving a temperature difference of 1.9°C. Chilled-water pressure gauges indicate approximately 4.5–5.0 bar, with no significant pressure difference observed. FINDINGS: Chiller is producing chilled water, with a measured temperature difference of 1.9°C. The relatively low temperature difference may indicate low cooling demand during operation. Overall visual condition is good, with no major external defects identified. Minor surface corrosion observed around pressure gauge connections and exposed piping. Electrical components appear visually intact.
Technical Details
- System
- Mechanical
- Category
- Chiller
- Manufacturer
- Trane
- Model
- RTAC 300J UICH
- Serial Number
- U16L06422
- Location
- —
Documents
0No documents attached.
Need to update this asset?
Sign in with your technician or administrator account. Your name and every changed field are added to the asset history.
Sign in to update