AtharAssetAsset Record
ATH-000106Rawabi · CMR

Air-Cooled Chiller 6

Status

Operational

Priority

P3 - Routine

Condition grade 3

Fair

1

2

3

4

5

FINDINGS & RECOMMENDED ACTION

Chiller visually inspected and found in generally acceptable condition, with minor external rusting and weathering. Compressor rated current is approximately 203 A per compressor, as indicated on the nameplate. Electrical current measurements recorded at 11.5 A and 10.2 A on the inspected circuits, with no abnormal current indicated by these readings. Chilled-water piping temperature readings recorded at 5.3°C and 9.0°C, indicating a temperature difference of 3.7°C. Water pressure gauges indicate approximately 4.5–5.0 bar, showing that the chilled-water circuit is pressurized. Electrical fuse holders and wiring appear generally intact, with no obvious signs of overheating.

Technical Details

System
Mechanical
Category
Chiller
Manufacturer
Trane
Model
RTAC 300J UICH
Serial Number
U15001819
Location
—