AtharAssetAsset Record
ATH-000110Rawabi · CMR

CHILLED WATER PUMP 4

Status

Operational

Priority

P3 - Routine

Condition grade 3

Fair

1

2

3

4

5

FINDINGS & RECOMMENDED ACTION

<Refer to attached images for measurement results> - Motor Casing > Below 70 °C > Satisfactory, no obvious overheating - Motor casing fins > Below 70 °C > Satisfactory, no obvious overheating - Motor drive-end bearing housing > Below 70 °C > Satisfactory, no obvious overheating. - Coupling guard > Below 70 °C > Satisfactory, no obvious overheating. - Pump bearing housing > Below 70 °C > Satisfactory, no obvious overheating. - Motor amperage > 42.0 A out of 42 A rated > No overcurrent detected. - Motor RPM > 1709 RPM out of 1750 RATED RPM > Within satisfactory range.

Technical Details

System
Mechanical
Category
Chilled Water Pump
Manufacturer
ABB
Model
4G12-1/2BF
Serial Number
543GJ163
Location
—

Documents

0

No documents attached.

Need to update this asset?

Sign in with your technician or administrator account. Your name and every changed field are added to the asset history.