Package Unit 1
Location
1ST FLOOR ROOF
Status
Operational
Priority
P4 - Monitor
Condition grade 3
Fair
1
2
3
4
5
FINDINGS & RECOMMENDED ACTION
- The unit is rated at 27 TR at T1 - Compressor + blower motor draw 45.2 A (No overcurrent) - ESP Measured > 610 Pa, abnormally high. - One compressor working due to low cooling demand. - Actual airflow > 10,876 CFM - Psychometric readings pre-coil @41% RH & 23.3 Celsius: Dry-bulb(Input) 23.3 °C RH(Input) 41.0 % Humidity ratio 7.29 g/kg Enthalpy 42.0 kJ/kg Wet-bulb 15.1 °C Dew point 9.3 °C Specific volume 0.850 m³/kg Density 1.186 kg/m³ Vapor pressure 1173 Pa - Psychometric readings pre-coil @53% RH & 16.5 Celsius: Dry-bulb(Input) 16.5 °C RH(Input) 53.0 % Humidity ratio 6.17 g/kg Enthalpy 32.2 kJ/kg Wet-bulb 11.3 °C Dew point 6.9 °C Specific volume 0.829 m³/kg Density 1.214 kg/m³ Vapor pressure 995 Pa Calculations: Total cooling load > 17.1 TR Sensible cooling load > 12.1 TR Latent cooling load > 5 TR FINDINGS: - One compressor running achieving 17.1 TR at maximum airflow. - Motor blower sound excessive > bearing to be changed.
Technical Details
- System
- Mechanical
- Category
- Package Unit
- Manufacturer
- Zamil
- Model
- PY350
- Serial Number
- CFNBN0012M
- Location
- 1ST FLOOR ROOF
Documents
0No documents attached.
Need to update this asset?
Sign in with your technician or administrator account. Your name and every changed field are added to the asset history.