Package Unit 2
Location
1ST FLOOR ROOF
Status
Operational
Priority
P3 - Routine
Condition grade 3
Fair
1
2
3
4
5
FINDINGS & RECOMMENDED ACTION
- Unit's rated T1 cooling capacity > 324000 BTU/h > 27 TR - Unit's actual airflow > 1.8 m^3/s - Unit actual ESP > 590 Pa - Unit's total current draw is 17.4 Amps, (no overcurrent detected) - PSYCHOMETRIC CALCULATIONS: READINGS AT Pre-coil Temp & % RH; 23.9 Celsius @ 42.3% RH: Dry-bulb(Input) 23.9 °C RH(Input) 42.3 % Humidity ratio 7.80 g/kg Enthalpy 43.9 kJ/kg Wet-bulb 15.7 °C Dew point 10.3 °C Specific volume 0.852 m³/kg Density 1.183 kg/m³ Vapor pressure 1255 Pa READINGS AT Post-coil temp & %RH; 9.4 Celsius @ 76.7% RH: Dry-bulb(Input) 9.4 °C RH(Input) 76.7 % Humidity ratio 5.60 g/kg Enthalpy 23.6 kJ/kg Wet-bulb 7.4 °C Dew point 5.5 °C Specific volume 0.808 m³/kg Density 1.245 kg/m³ Vapor pressure 905 Pa Summary of calculations: Total cooling load > 12.5 TR Sensible cooling load > 9.1 TR Latent cooling load > 3.4 TR Unit's rated T1 cooling capacity is 27 TR, while calculated cooling duty under actual site conditions and only one compressor running is approximately 12.5 TR.
Technical Details
- System
- Mechanical
- Category
- Package Unit
- Manufacturer
- Zamil
- Model
- PY350
- Serial Number
- HSA101 - 00005680
- Location
- 1ST FLOOR ROOF