AtharAssetAsset Record
ATH-000174Rawabi · CMR

Package Unit 3

Location

1ST FLOOR ROOF

Status

Operational

Priority

P4 - Monitor

Condition grade 2

Good

1

2

3

4

5

FINDINGS & RECOMMENDED ACTION

- Rated @ 20 TR- Actual Airflow > 7720 CFM > 3.6 m^3/s READINGS AT Pre-coil Temp & % RH; 22.6 Celsius @ 34.2% RH: Dry-bulb(Input) 22.6°C RH(Input) 34.2% Humidity ratio 5.81g/kg Enthalpy 37.5kJ/kg Wet-bulb13.4°C Dew point 6.0 °C Specific volume 0.846 m³/kg Density 1.189 kg/m³ Vapor pressure 938Pa READINGS AT Post-coil temp & %RH; 10.7 Celsius @ 74% RH: Dry-bulb(Input) 10.7°C RH(Input) 74.0% Humidity ratio 5.90g/kg Enthalpy 25.6kJ/kg Wet-bulb8.4 °C Dew point 6.3 °C Specific volume 0.812 m³/kg Density 1.239 kg/m^3 Vapor pressure 952Pa Summary of calculations: Total cooling load > 14.6 TR > - Unit's cooling demand was low, second compressor could not start for full performance check

Technical Details

System
Mechanical
Category
Package Unit
Manufacturer
LG
Model
AK-Q270C01
Serial Number
504SACZ2V446
Location
1ST FLOOR ROOF

Documents

0

No documents attached.