Package Unit 8
Location
1ST FLOOR ROOF
Status
Operational
Priority
P4 - Monitor
Condition grade 2
Good
1
2
3
4
5
FINDINGS & RECOMMENDED ACTION
- Unit rated capacity > 23 TR - Actual airflow > 6,269 CFM > 2.9 m3^/s - PSYCHOMETRIC CALCULATIONS: READINGS AT Pre-coil Temp & % RH; 22.6 Celsius @ 34.2% RH: Dry-bulb(Input) 22.6 °C RH(Input) 34.2 % Humidity ratio 5.81 g/kg Enthalpy 37.5 kJ/kg Wet-bulb 13.4 °C Dew point 6.0 °C Specific volume 0.846 m³/kg Density 1.189 kg/m³ Vapor pressure 938 Pa READINGS AT Post-coil temp & %RH; 10.7 Celsius @ 74% RH: Dry-bulb(Input) 10.7 °C RH(Input) 74.0 % Humidity ratio 5.90 g/kg Enthalpy 25.6 kJ/kg Wet-bulb 8.4 °C Dew point 6.3 °C Specific volume 0.812 m³/kg Density 1.239 kg/m³ Vapor pressure 952 Pa Summary of calculations: Total cooling load > 11.8 TR > 12 TR Sensible - Unit's cooling demand was low, second compressor could not start for full performance check.
Technical Details
- System
- Mechanical
- Category
- Package Unit
- Manufacturer
- LG
- Model
- AK-Q3009C01
- Serial Number
- 109SAAB0F024
- Location
- 1ST FLOOR ROOF