ATH-000180Rawabi · CMR

Package Unit 9

Location

2nd FLOOR ROOF

Status

Operational

Priority

P4 - Monitor

Condition grade 3

Fair

1

2

3

4

5

FINDINGS & RECOMMENDED ACTION

- Unit has been found to be supporting AHU due to both ducts having positive supply-like pressure. - Rated at 27 TR - Actual airflow > 6.1 m3/s > 13,031 CFM - Actual ESP > 450 Pa - Blower motor drawing 9.3 A out of 11 RATED. NO OVERCURRENT DETECTED. Psychometric readings @16 Celsius & 44.1% RH: Dry-bulb(Input) 16.0 °C RH(Input) 41.4 % Humidity ratio 4.66 g/kg Enthalpy 27.9 kJ/kg Wet-bulb 9.4 °C Dew point 2.9 °C Specific volume 0.825 m³/kg Density 1.217 kg/m³ Vapor pressure 753 Pa READINGS AT Post-coil temp & %RH’; 6.5 Celsius @ 66.9% RH: Dry-bulb(Input) 6.5 °C RH(Input) 66.9 % Humidity ratio 4.00 g/kg Enthalpy 16.6 kJ/kg Wet-bulb 4.0 °C Dew point 0.8 °C Specific volume 0.797 m³/kg Density 1.259 kg/m³ Vapor pressure 648 Pa Summary of calculations: Total cooling load > 23.5 TR Sensible cooling load > 20.2 TR Latent cooling load > 3.3 TR - Package unit is achieving 23.5 TR at maximum operation speed. 37 Degree Celsius ambient temperature.

Technical Details

System
Mechanical
Category
Package Unit
Manufacturer
Zamil
Model
PY350
Serial Number
HSA101 - 00005682
Location
2nd FLOOR ROOF

Documents

0

No documents attached.