ATH-000185Rawabi · CMR
Package Unit 14
Location
FINANCE ROOF
Status
Operational
Priority
P3 - Routine
Condition grade 3
Fair
1
2
3
4
5
FINDINGS & RECOMMENDED ACTION
- Supply static pressure measured at 230 Pa ; No abnormally high pressure detected - Extremely loud, bearing found to be the cause of noise since no overcurrent of blower motor detected.
Technical Details
- System
- Mechanical
- Category
- Package Unit
- Manufacturer
- CARRIER
- Model
- 50TJ-O16-531S
- Serial Number
- IX UP255 0145
- Location
- FINANCE ROOF