AtharAssetAsset Record
ATH-000187Rawabi · CMR

Package Unit 16

Location

5TH FLOOR

Status

Operational

Priority

P3 - Routine

Condition grade 2

Good

1

2

3

4

5

FINDINGS & RECOMMENDED ACTION

- Unit rated at 27 TR - Unit's full load at 16.8 Amps (motors and compressors) - Unit's blower motor load @ 11.4 A against rated 15.6. No overcurrent detected. - Actual External Static Pressure measured > 590 Pascals - Actual airflow measured > 4.3 m^3/s > 9,012 CFM - PSYCHOMETRIC CALCULATIONS: READINGS AT Pre-coil Temp & % RH; 23.7 Celsius @ 29.4% RH: Dry-bulb(Input) 23.7 °C RH(Input) 29.4 % Humidity ratio 5.34 g/kg Enthalpy 37.4 kJ/kg Wet-bulb 13.4 °C Dew point 4.8 °C Specific volume 0.848 m³/kg Density 1.185 kg/m³ Vapor pressure 862 Pa READINGS AT Post-coil temp & %RH’; 9.7 Celsius @ 77.5% RH: Dry-bulb(Input) 9.7 °C RH(Input) 77.5 % Humidity ratio 5.78 g/kg Enthalpy 24.3 kJ/kg Wet-bulb 7.8 °C Dew point 6.0 °C Specific volume 0.809 m³/kg Density 1.244 kg/m³ Vapor pressure 933 Pa Summary of calculations: Total cooling load > 19.2 TR ; SENSIBLE COOLING

Technical Details

System
Mechanical
Category
Package Unit
Manufacturer
Zamil
Model
PY350
Serial Number
HAS101 - 00005684
Location
5TH FLOOR

Documents

0

No documents attached.

Need to update this asset?

Sign in with your technician or administrator account. Your name and every changed field are added to the asset history.

Sign in to update