Package Unit 22
Location
1ST FLOOR ROOF
Status
Operational
Priority
P3 - Routine
Condition grade 2
Good
1
2
3
4
5
FINDINGS & RECOMMENDED ACTION
- Unit's rated T1 cooling capacity > 154,000 BTU/h > 13 TR - Unit's actual airflow > 1.8 m^3/s > 3,929 CFM - Unit's supply fan actual ESP > 310 Pascals - PSYCHOMETRIC CALCULATIONS: READINGS AT Pre-coil Temp & % RH; 27.2 Celsius @ 36.2% RH: Dry-bulb(Input) 27.2 °C RH(Input) 36.2 % Humidity ratio 8.12 g/kg Enthalpy 48.1 kJ/kg Wet-bulb 17.2 °C Dew point 10.9 °C Specific volume 0.862 m3/kg Density 1.170 kg/m3 Vapor pressure 1307 Pa READINGS AT Post-coil temp & %RH’; 13.7 Celsius @ 55.9% RH: Dry-bulb(Input) 13.7 °C RH(Input) 55.9 % Humidity ratio 5.43 g/kg Enthalpy 27.5 kJ/kg Wet-bulb 9.2 °C Dew point 5.1 °C Specific volume 0.820 m3/kg Density 1.227 kg/m3 Vapor pressure 876 Pa Summary of calculations: Total cooling load > 12.7 TR
Technical Details
- System
- Mechanical
- Category
- Package Unit
- Manufacturer
- Carrier
- Model
- 50TCMD14B2
- Serial Number
- 09 21 S 25795
- Location
- 1ST FLOOR ROOF
Documents
0No documents attached.
Need to update this asset?
Sign in with your technician or administrator account. Your name and every changed field are added to the asset history.
Sign in to update