AtharAssetAsset Record
ATH-000194Rawabi · CMR

Package Unit 23

Location

3rd Floor - AHU 15

Status

Operational

Priority

P1 - Urgent

Condition grade 5

Critical

1

2

3

4

5

FINDINGS & RECOMMENDED ACTION

- Rated at 27 TR - Actual Measured Airflow > 2.24 m3/s > 4,766 CFM - ESP Measured > 670 Pa > Obvious Airflow restriction - Psychrometric readings pre-coil @43.6% RH & 23.6 Celsius dry bulb temperature: Dry-bulb(Input) 23.6 °C RH(Input) 43.6 % Humidity ratio 7.90 g/kg Enthalpy 43.8 kJ/kg Wet-bulb 15.7 °C Dew point 10.5 °C Specific volume 0.851 m³/kg Density 1.184 kg/m³ Vapor pressure 1271 Pa Psychrometric readings post-coil @63.6% RH & 20.4 Celsius dry bulb temperature: Dry-bulb(Input) 20.4 °C RH(Input) 63.6 % Humidity ratio 9.50 g/kg Enthalpy 44.6 kJ/kg Wet-bulb 16.0 °C Dew point 13.3 °C Specific volume 0.844 m³/kg Density 1.196 kg/m³ Vapor pressure 1525 Pa - Negative cooling load - Compressor and refrigeration cycle not working ; malfunction.

Technical Details

System
Mechanical
Category
Package Unit
Manufacturer
Zamil
Model
PY350
Serial Number
HSA101 - 00005677
Location
3rd Floor - AHU 15

Documents

0

No documents attached.