Return Fan 1061
Location
2ND FLOOR
Status
Operational
Priority
P4 - Monitor
Condition grade 2
Good
1
2
3
4
5
FINDINGS & RECOMMENDED ACTION
- Fan motor rated @ 1725 RPM - Motor fan measured RPM: 1787 (Rated 1750) - Pulley motor diameter: 15 cm - Pulley fan diameter: 21 cm -Pulley-to-pulley ratio: 14.4/20.4 = 0.706 - Expected Fan Pulley RPM > 1787 * 0.706 cm = 1262 RPM - Actual fan pulley RPM: 1155 RPM - Belt Slippage: 8.5% - NEEDS checking and proper tensioning for power transmission. - No obvious overheating found - Stable & equal parallel bearing temperature > thermally no signs of misalignment or overloading. - Motor current 13.6 Amps out of 15.2 Rated (No overcurrent detected)
Technical Details
- System
- Mechanical
- Category
- Return Fan
- Manufacturer
- —
- Model
- 3030A/9R
- Serial Number
- 2574
- Location
- 2ND FLOOR