ATH-000451Rawabi · CMR

R.O plan 1

Location

AL-FARIS

Status

Operational

Priority

P3 - Routine

Condition grade 3

Fair

1

2

3

4

5

FINDINGS & RECOMMENDED ACTION

RO membrane vessels visually inspected and found in good external condition. No major corrosion, leakage or structural damage observed. First-stage operating pressure recorded at 11.2 bar. Second-stage operating pressure recorded at 13.5 bar. Inlet pressure recorded between 0–1 bar. TDS before RO recorded at 749 ppm. TDS after RO recorded at 123 ppm. Calculated TDS rejection efficiency is 83.6%, relatively low compared to typical RO membrane performance. Low TDS rejection indicates possible membrane fouling, scaling, deterioration or internal seal bypass. Electrical current readings recorded at 38.9 A, 40.0 A and 38.4 A, with no major current imbalance. RO plant and feed pump observed running during inspection.

Technical Details

System
Plumbing & Water
Category
Reverse Osmosis
Manufacturer
FROTEC
Model
NA
Serial Number
NA
Location
AL-FARIS

Documents

0

No documents attached.

Need to update this asset?