Fan Coil Unit 1
Location
Basement Gen Room
Status
Operational
Priority
P3 - Routine
Condition grade 3
Fair
1
2
3
4
5
FINDINGS & RECOMMENDED ACTION
- Actual Airflow at full capacity > 0.42 m3/s > 886 CFM Psychometric readings @79.9% RH & 11.7 Celsius dry bulb temperature: Dry-bulb(Input) 11.7 °C RH(Input) 79.9 % Humidity ratio 6.82 g/kg Enthalpy 29.0 kJ/kg Wet-bulb 9.9 °C Dew point 8.4 °C Specific volume 0.816 m³/kg Density 1.234 kg/m³ Vapor pressure 1099 Pa Psychometric readings @44.9% RH & 20 Celsius dry bulb temperature: Dry-bulb(Input) 20.0 °C RH(Input) 44.9 % Humidity ratio 6.51 g/kg Enthalpy 36.7 kJ/kg Wet-bulb 13.1 °C Dew point 7.7 °C Specific volume 0.839 m³/kg Density 1.199 kg/m³ Vapor pressure 1050 Pa Summary of calculations: Total cooling load > 1.1 TR - Unit is cooling return conditioned air continuously even at full operation, therefore, no suspected underperforming despite only 1.1 TR achievement at full load.
Technical Details
- System
- Mechanical
- Category
- Air Handling Unit
- Manufacturer
- Not recorded
- Model
- Not recorded
- Serial Number
- Not recorded
- Location
- Basement Gen Room