AtharAssetAsset Record
ATH-000453Rawabi · CMR

Fan Coil Unit 1

Location

Basement Gen Room

Status

Operational

Priority

P3 - Routine

Condition grade 3

Fair

1

2

3

4

5

FINDINGS & RECOMMENDED ACTION

- Actual Airflow at full capacity > 0.42 m3/s > 886 CFM Psychometric readings @79.9% RH & 11.7 Celsius dry bulb temperature: Dry-bulb(Input) 11.7 °C RH(Input) 79.9 % Humidity ratio 6.82 g/kg Enthalpy 29.0 kJ/kg Wet-bulb 9.9 °C Dew point 8.4 °C Specific volume 0.816 m³/kg Density 1.234 kg/m³ Vapor pressure 1099 Pa Psychometric readings @44.9% RH & 20 Celsius dry bulb temperature: Dry-bulb(Input) 20.0 °C RH(Input) 44.9 % Humidity ratio 6.51 g/kg Enthalpy 36.7 kJ/kg Wet-bulb 13.1 °C Dew point 7.7 °C Specific volume 0.839 m³/kg Density 1.199 kg/m³ Vapor pressure 1050 Pa Summary of calculations: Total cooling load > 1.1 TR - Unit is cooling return conditioned air continuously even at full operation, therefore, no suspected underperforming despite only 1.1 TR achievement at full load.

Technical Details

System
Mechanical
Category
Air Handling Unit
Manufacturer
Not recorded
Model
Not recorded
Serial Number
Not recorded
Location
Basement Gen Room