Fan Coil Unit 2
Location
Basement Gen Room
Status
Operational
Priority
P3 - Routine
Condition grade 3
Fair
1
2
3
4
5
FINDINGS & RECOMMENDED ACTION
- Actual Measured Airflow > 0.3 m3/s > 607 CFM Psychometric reading of pre-coil @ 42% RH & 21 Celsius dry bulb temperature: Dry-bulb(Input) 21.0 °C RH(Input) 42.0 % Humidity ratio 6.48 g/kg Enthalpy 37.6 kJ/kg Wet-bulb 13.4 °C Dew point 7.6 °C Specific volume 0.842 m³/kg Density 1.195 kg/m³ Vapor pressure 1045 Pa Psychometric reading of post-coil @ 79% RH & 10 Celsius dry bulb temperature: Dry-bulb(Input) 10.0 °C RH(Input) 79.0 % Humidity ratio 6.01 g/kg Enthalpy 25.2 kJ/kg Wet-bulb 8.2 °C Dew point 6.5 °C Specific volume 0.810 m³/kg Density 1.242 kg/m³ Vapor pressure 970 Pa Summary of calculations: Total cooling load > 1.27 TR Sensible cooling load > 1.15 TR Latent cooling load > 0.12 TR FINDINGS: - Unit was tested at normal thermostat operation setpoint. - Achieved 1.26 TR total cooling at medium fan speed and 22 Celsius thermostat setpoint.