ATH-000455Rawabi · CMR
Fan Coil Unit 3
Location
Basement
Status
Operational
Priority
P2 - Planned
Condition grade 3
Fair
1
2
3
4
5
FINDINGS & RECOMMENDED ACTION
- Actual Airflow at full capacity > 0.042 m3/s > 90 CFM Psychometric readings post-coil @48% RH & 21.2 Celsius dry bulb temperature: Dry-bulb(Input) 21.2 °C RH(Input) 48.0 % Humidity ratio 7.51 g/kg Enthalpy 40.4 kJ/kg Wet-bulb 14.5 °C Dew point 9.8 °C Specific volume 0.844 m³/kg Density 1.194 kg/m³ Vapor pressure 1209 Pa FINDINGS: - Unit is operating achieving 9.6 Celsius reduction for small commander room requirement. - Occupier complains about fan noise.
Technical Details
- System
- Mechanical
- Category
- Air Handling Unit
- Manufacturer
- N/A
- Model
- N/A
- Serial Number
- N/A
- Location
- Basement
Documents
0No documents attached.