AtharAssetAsset Record
ATH-000455Rawabi · CMR

Fan Coil Unit 3

Location

Basement

Status

Operational

Priority

P2 - Planned

Condition grade 3

Fair

1

2

3

4

5

FINDINGS & RECOMMENDED ACTION

- Actual Airflow at full capacity > 0.042 m3/s > 90 CFM Psychometric readings post-coil @48% RH & 21.2 Celsius dry bulb temperature: Dry-bulb(Input) 21.2 °C RH(Input) 48.0 % Humidity ratio 7.51 g/kg Enthalpy 40.4 kJ/kg Wet-bulb 14.5 °C Dew point 9.8 °C Specific volume 0.844 m³/kg Density 1.194 kg/m³ Vapor pressure 1209 Pa FINDINGS: - Unit is operating achieving 9.6 Celsius reduction for small commander room requirement. - Occupier complains about fan noise.

Technical Details

System
Mechanical
Category
Air Handling Unit
Manufacturer
N/A
Model
N/A
Serial Number
N/A
Location
Basement

Documents

0

No documents attached.

Need to update this asset?

Sign in with your technician or administrator account. Your name and every changed field are added to the asset history.

Sign in to update