Fan Coil Unit 4
Location
Basement
Status
Operational
Priority
P2 - Planned
Condition grade 4
Poor
1
2
3
4
5
FINDINGS & RECOMMENDED ACTION
- Thermostat set at 8 Celsius and maximum speed. - Actual Airflow > 0.67 m3/s > 1,426 CFM Psychometric readings post-coil @67% RH & 15.6 Celsius dry bulb temperature: Dry-bulb(Input) 15.6 °C RH(Input) 67.0 % Humidity ratio 7.38 g/kg Enthalpy 34.4 kJ/kg Wet-bulb 12.1 °C Dew point 9.5 °C Specific volume 0.828 m³/kg Density 1.217 kg/m³ Vapor pressure 1188 Pa Psychometric readings pre-coil @39.4% RH & 25.9 Celsius dry bulb temperature: dry-bulb(Input) 25.9 °C RH(Input) 39.4 % Humidity ratio 8.19 g/kg Enthalpy 46.9 kJ/kg Wet-bulb 16.8 °C Dew point 11.1 °C Specific volume 0.858 m³/kg Density 1.175 kg/m³ Vapor pressure 1317 Pa Calculations: Total cooling load > 2.9 TR FINDINGS: FCU operated at maximum fan speed with thermostat set at 8°C. Actual airflow measured at approximately 1,426 CFM. Pre-coil temperature recorded at 25.9°C and post-coil temperature at 15.6°C, achieving a temperature reduction of 10.3°C. Calculated total cooling duty approximately 2.9 TR, including 2.4 TR sensible and 0.5 TR latent cooling. Unit demonstrates effective cooling and moisture removal under actual operating conditions. HOWEVER, the supporting FCU is defect and not working, making the room temperature only 25 Celsius (electrical large room) having the FCU work all by itself to achieve required cooling demand. Replace of the FCU (to the elevator 1 side) is recommended immediately to support the full room load.
Technical Details
- System
- Mechanical
- Category
- Air Handling Unit
- Manufacturer
- N/A
- Model
- N/A
- Serial Number
- N/A
- Location
- Basement
Documents
0No documents attached.
Need to update this asset?
Sign in with your technician or administrator account. Your name and every changed field are added to the asset history.
Sign in to update