Chiller 2
Status
Operational
Priority
P3 - Routine
Condition grade 3
Fair
1
2
3
4
5
FINDINGS & RECOMMENDED ACTION
Unit visually inspected and found in fair overall condition. Chilled water return temperature measured at 8°C. Chilled water supply temperature measured at 5°C. Temperature difference measured at 3°C, indicating heat absorption across the evaporator, although lower than the typical 5–6°C design differential. Return chilled water pressure measured at 108 PSI (7.45 bar). Supply chilled water pressure unavailable; differential water pressure could not be calculated. One pressure gauge found severely deteriorated, with its dial completely unreadable. Visible surface corrosion and aging observed around pressure gauge fittings and connections. Chilled water pipe insulation shows signs of deterioration and damaged external wrapping. No major external structural damage observed on the chiller casing.
Technical Details
- System
- Mechanical
- Category
- Chiller
- Manufacturer
- TRane
- Model
- RTAC 400 J
- Serial Number
- U14A9B107
- Location
- —