AtharAssetAsset Record
ATH-000467Al-Salam

Chiller 2

Status

Operational

Priority

P3 - Routine

Condition grade 3

Fair

1

2

3

4

5

FINDINGS & RECOMMENDED ACTION

Unit visually inspected and found in fair overall condition. Chilled water return temperature measured at 8°C. Chilled water supply temperature measured at 5°C. Temperature difference measured at 3°C, indicating heat absorption across the evaporator, although lower than the typical 5–6°C design differential. Return chilled water pressure measured at 108 PSI (7.45 bar). Supply chilled water pressure unavailable; differential water pressure could not be calculated. One pressure gauge found severely deteriorated, with its dial completely unreadable. Visible surface corrosion and aging observed around pressure gauge fittings and connections. Chilled water pipe insulation shows signs of deterioration and damaged external wrapping. No major external structural damage observed on the chiller casing.

Technical Details

System
Mechanical
Category
Chiller
Manufacturer
TRane
Model
RTAC 400 J
Serial Number
U14A9B107
Location
—

Documents

0

No documents attached.

Need to update this asset?

Sign in with your technician or administrator account. Your name and every changed field are added to the asset history.

Sign in to update